Flue connection
The joint between the Thermostove and the ue
must be installed using suitable tubes (min. T200).
Use is forbidden of exible metal tubes, in cement
bre or aluminium. The slope of the smoke duct
must not have horizontal sections over 2 metres
and must have a minimum 3% inclination. The
rst change of direction must take place after at
least 1.5 metres of the vertical section. Inspect the
base of the smoke duct
with periodic controls. It is forbidden to connect
the same smoke duct on multiple equipment. Keep
the smoke duct an adequate distance from any
ammable parts or parts sensitive to heat. Refer to
the instructions given by the manufacturer of the
ue for the distances to respect.
Remote Control
The remote control (Fig. 3) used to adjust water temperature
power and the on/off functions for the pellet Thermostove.
To start the Thermostove, press key
automatically enter the starting phase.
Press keys + (1) and - (2) to adjust temperature, and use keys
+ (6) and - (5) to adjust operating power.
To turn off the Thermostove, hold down key .
To replace the 3 volt battery located on the back of the remote
control, pull the centre of the cover and the lever on the side
of the same, replace the battery observing the correct polarity
(Fig. 4)
10
F
3
and the Thermostove will
1
U
E
V
I
D
I
U
I
4
T
I
U= INSULATION
A= MINIMUM 40 MM
V= POSSIBLE REDUCTION FROM 100 TO 80 MM
B=MASSIMUM 4 M
I= INSPECTION PLUG
C= MINIMUM 3°
S= INSPECTION DOOR
D= MINIMUM 400 MM
P= AIR INTAKE
E= DIAMETER OF HOLE
T= T JOINT WITH INSPECTION PLUG
F= SEE FIG. 2-3-4-5-6