External Sensor - Sime MURELLE HE 25 BF Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3.4

EXTERNAL SENSOR

ES
If there is an external sensor, the heating
PT
settings SET can be taken from the climatic
curves according to the external tempera-
ture and, in any case, limited to with the
GB
range values described in point 3.3 (para-
meters PAR 25 for zone 1 and PAR 26 for
zone 2). The climatic curve to be set can be
selected from a value of 3 and 40 (at step
1). Increasing the steepness of the curves
of fig. 13 will increase the output tempera-
ture as the external temperature decrea-
ses.
3.5
CARD FUNCTIONING
The electronic card has the following func-
tions:
– Antifreeze protection of the heating
and sanitary water circuits (ICE).
– Ignition and flame detection system.
– Control panel setting for the power and
the gas for boiler functioning.
– Anti-block for the pump which is fed for
a few seconds after 24 hours of inacti-
vity.
– Antifreeze protection for boilers with
an accumulation boiling unit.
– Chimney sweep function which can be
activated from the control panel.
– Temperature which can be shifted with
the external sensor connected.
It can be set from the control panel and
is active on the heating systems of both
circuit 1 and circuit 2.
– Management of two independent hea-
ting circuit systems.
– Automatic regulation of the ignition
power and maximum heating.
Adjustments are managed automati-
cally by the electronic card to guaran-
tee maximum flexibility in use of the
system.
– Interface with the following electronic
systems: climatic regulator CR 53,
remote control CR 73, thermal regula-
tor RVS and connected to a manage-
ment card of a mixed zone cod.
8092233.
NOTE: If using CR 53 or RVS set para-
meter 10 to 2 (PAR 10 = 2).
3.6
TEMPERATURE
DETECTION SENSOR
Table 4 shows the resistance values of the
heating, DHW and exhaust fumes thermi-
stors.
If the heating sensor (SM) is faulty or
open circuit, the boiler will not function on
either heating or DHW (ALL 05).
If the exhaust fumes sensor (SF) is faulty
or open circuit, the boiler will not function
on either heating or DHW (ALL 14).
If the DHW sensor (SS) is faulty or open
circuit, the boiler will work without modu-
lation to the DHW temperature.
88
ATTENTION: curves are calculated at an ambient temperature of 20°C. It is
however possible to use the boiler controls to change them by ±5°C.
TABLE 4 (SM - SS - SF sensors)
Temperature (°C)
Resistance (Ω)
20
12.090
30
8.313
40
5.828
50
4. 1 61
60
3.021
70
2.229
80
1.669
3.7
ELECTRONIC
IGNITION
Ignition and flame detection is controlled
by a single electrode on the burner which
guarantees reaction in the case of acci-
dental extinction or lack of gas within one
second.
3.7. 1
Functioning cycle
Burner ignition occurs within max. 10
seconds after the opening of the gas
valve. Ignition failure with consequent acti-
vation of block can be due to:
– Lack of gas
The ignition electrode persists in
discharging for max. 10 seconds. If the
burner does not ignite, the anomaly is
signalled.
This can happen the first time the boi-
ler is switched on after a long period of
inactivity due to the presence of air in
the gas pipes
It can be caused by a closed gas tap or
by a broken valve coil (the interruption
does not allow for opening).
– The electrode does not discharge.
In the boiler, only the opening of the gas
to the burner can be detected. After
10 seconds the anomaly is signalled. It
can be caused by an interruption in the
electrode wire or if it is incorrectly
anchored to the connection points. Or
the electrode may be earthed or stron-
gly worn: it must be replaced.
Or the electronic card may be defecti-
ve.
– No flame detected
After start-up the electrode continues
to discharge even when the burner is
on. After 10 seconds, the discharge
stops, the burner is switched off and a
fault is generated.
This fault is sometimes caused by the
shorting of the electrode cable or by its
improper fixing to the connection
points. The electrode is connected to
the earth or badly worn and must be
replaced. The electronic board is faulty.
In the case of a sudden lack of voltage, the
burner will immediately switch off. When
voltage returns, the boiler will automatically
start up again.
Fig. 13

Publicidad

Tabla de contenido
loading

Tabla de contenido