Code 191 (High Water Level); Code 205 (Level Switch Inconsistency); Code 225 (Communication Error Pump Module); Code 226 (Communication Error Io Module) - Grundfos LC 241 Manual Del Usuario

Ocultar thumbs Ver también para LC 241:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The alarm symbol on the display turns red and the pump
stops.
Alarm code Signal fault is displayed in Grundfos GO Remote.
Cause
The signal from the sensor is out of the configured range.
Remedy
Go to Settings > Level control in Grundfos GO Remote and
ensure that the configured range corresponds to the physical
application type.
Change the sensor, if needed.

8.15 Code 191 (High water level)

Alarm code 191 is shown on the display.
The alarm symbol on the display turns red, but the pump's
operating mode is unchanged.
Alarm code High water level is displayed in Grundfos GO
Remote.
Cause
The defined start level did not start the pump.
Remedy
Check and configure the sensor for start level.
Cause
The pump is not big enough to remove the water.
Remedy
Contact Grundfos or an authorized service workshop.
Cause
The level sensor is defective and not reacting on level changes.
Remedy
Check the functionality of the level sensor.
Related information
3.6 Configuring the input and output terminals using Grundfos GO
Remote

8.16 Code 205 (Level switch inconsistency)

Alarm code 205 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Level switch inconsistency is displayed in
Grundfos GO Remote.
Cause
A float switch could be defective or stuck.
Remedy
Check the functionality of each float switch.
Related information
3.6 Configuring the input and output terminals using Grundfos GO
Remote

8.17 Code 225 (Communication error pump module)

Alarm code 225 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Communication fault, pump module is displayed
in Grundfos GO Remote.
The product is unable to communicate with the IO module.
Cause
The connection to GENIbus is missing.
Remedy
Check the GENIbus connection cable between CU 24X and
IO 242.
Cause
The pump module is defective.
Remedy
Contact Grundfos.

8.18 Code 226 (Communication error IO module)

Alarm code 226 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Communication fault, I/O module is displayed in
Grundfos GO Remote.
The product is unable to communicate with the IO module.
Cause
The connection to GENIbus is missing.
Remedy
Check the GENIbus connection cable between CU 24X and
IO 241.
Cause
The IO module is defective.
Remedy
Contact Grundfos.

8.19 Code 229 (Water on floor)

Warning code 229 is shown on the display if you press
the Up or Down button.
The warning symbol on the display turns yellow and the pump's
operating mode is unchanged.
Warning code Water on floor is displayed in Grundfos GO
Remote.
Cause
The sensor detects water on the floor.
Remedy
Check for water leakage.
25