ZENITH-P
ENGLISH
CONTENTS
1. Installation, operation and maintenance instructions for safe use
2. Technical data
3. Installation
4. Servicing and maintenance and repairing
THIS DOCUMENT MUST BE READ CAREFULLY BEFORE INSTALLATION
These instructions are intended for: expert electricians or appropriately trained personnel.
1. INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR SAFE USE
1.1 SAFETY RULES
Enclosures type ZENITH-P are designed as Group II Category 2 equipment and is suitable for use for fixed installation in areas with
explosion hazard designated Zone 1 / Zone 2 and Zone 21 / Zone 22.
These operating instructions must be kept in safe place for later consultation. During operation, do not leave this instruction manual
or other objects in the enclosure.
Operate the enclosures type ZENITH-P only for their intended duty in the undamaged and clean condition, and only where the
resistance of the material to the surroundings is assured.
The enclosures are designed to withstand an impact of 7 J, and to be used in normal conditions of vibration. They are not designed
for use in areas subject to intentional or extreme conditions of vibration.
Enclosures are made of carbon loaded glass reinforced polyester. The enclosures have a surface resistance between 10
10
Ω. They do not present a hazard from static electricity.
9
In the event of incorrect assembly, the type of protection will no longer be assured.
Only genuine SCAME spare parts may be used for replacement.
No modifications are allowed to the enclosures that are not expressly mentioned in this instruction manual.
1.2 CONFORMITY TO STANDARDS
The enclosure ZENIYH-P empty enclosure are designed for Zone 1/21 and Zone 2/22 according to:
• EN 60079-0:2018
• EN 60079-7:2015
• EN 60079-31:2014
• IEC 60079-0:2017
• IEC 60079-7:2015
• IEC 60079-31:2013
They are manufactured and tested in accordance with ATEX directive 2014/34/EU, IECEx scheme, state-of-the-art engineering
practice and ISO 9001.
MP39688
12
12
13
14
19
and
6
ZP91041-2