Energi Savr Node
Product overview
WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power via circuit
breaker before wiring or servicing the Energi Savr NodeT with EcoSystemR unit.
Buttons and LEDs on the front of the unit are used for troubleshooting. If wiring is exposed when accessing buttons and
LEDs, the unit must be accessed by a certified electrician, following local codes.
The Energi Savr NodeT with EcoSystemR unit powers two ECO links and supports communication for a maximum of 64 EcoSystemR
ballasts or other controllable illumination drivers per link, 128 total. An Energi Savr NodeT with EcoSystemR system consists of
Energi Savr NodeT with EcoSystemR units, ballasts, inputs, wallstations, and QS devices. The diagram on the previous page shows a
typical system topology.
• All ballasts and Energi Savr NodeT with EcoSystemR units are powered by mains voltage (Live and Neutral).
• Two additional wires for digital communication per ECO link.
• The ECO link may be treated as mains voltage and thus may be run within the same conduit.
• The ECO link wires are non-polarised and can be run as a daisy chain, T-tap, star, or in any combination.
• The Energi Savr NodeT with EcoSystemR unit has inputs for:
– 128 total ballasts (64 per ECO link)
– 4 daylight sensors (model: EC-DIR-WH)
– 4 occupancy sensors (models: Lutron LOS series)
– 4 IR receivers (models: EC-DIR-WH, EC-IR-WH)
• The QS Link can have up to 100 zones and 100 devices.
• The Energi Savr NodeT with EcoSystemRunit occupies 1 device position and up to 100 zone positions.
• In a system with multiple Energi Savr NodeT with EcoSystemR units, a maximum of 100 daylight sensors and 100 occupancy
sensors are permitted.
Refer to the following step-by-step guide for proper Energi Savr NodeT with EcoSystemR unit installation.
– To connect multiple Energi Savr NodeT with EcoSystemR units into a single system, use the QS link (pin 1, 3, and 4 only).
See PELV Wiring Example on page 8 for more details.
Wiring overview
PELV
Inputs
Mains
Wiring
Lutron
2
|
®
with EcoSystemR
TM
Ethernet
Eco
QS
Programming
Link 1
Link
Port
|
Installation Guide
Eco
Link 2
International Energi Savr Node
with EcoSystemR Installation Guide
TM