Example: Conductor
Size
(general)
(mm²)
2.5
16
25
The calculation is made as follows: In the example above, the terminal
assignment table shows that, for a load of 15 A, up to 38 wires fit in
19 2.5-mm² terminals. Thus, 12 wires correspond to 32% of the total
permitted number.
In the event that the maximum load limit is exceeded as a result of the
number of conductors used, then it will be necessary to de-rate the current
of the conductors to ensure compliance with the applicable terminal content
tables. For example:
The following table shows how the maximum load limit has been exceeded
(i.e. load is 128%).
Example: Conductor
size
(general)
(mm²)
2.5
16
In the following table, the maximum current of 6 conductors has been de-
rated to 15 A (2.5 mm² conductor) and 4 conductors has been de-rated to
50 A (16 mm² conductor) in order to ensure that the maximum load limit for
the enclosure does not exceed 100%.
26
Current
Number of
conductors
(A)
15
12 (of 38)
50
8 (of 26)
66
8 (of 25)
Total:
Current
Number of
conductors
(A)
21
12 (of 18)
66
8 (of 13)
Total:
Load
32%
31%
32%
94%
< 100%
Load
67%
62%
128%
< 100%