F1
Output protection fuse for motor and blinker
F2
Protection fuse of transformer
F3
Output protection fuse of accessories and signals
The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting
the desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
Other special functions follow the parameters and logic menus and may vary depending on the type of control unit or the software
release.
The CP.BULL-RI and MATRIX control units are equipped with a built-in radio module to receive both
fixed code and variable code control signals with a frequency of 433.92MHz, able to store up to 64 different codes in memory.
The RADIO menu and the 2Ch and CVAR logic are available in these control units only.
The CP.BULL and MATRIX-RE control units are equipped with connector for extractable receiver.
1 Press the button <PG>, the display goes to the first menu, Parameters "PAR".
2 With the <+> or <-> button, select the menu you want (PAR>>LOG>>RADIO>>NMAN>>RES)
3 Press the button <PG>, the display shows the first function available on the menu.
4 With the <+> or <-> button, select the function you want.
5 Press the button <PG>, the display shows the value currently set for the function selected.
6 With the <+> or <-> button, select the value you intend to assign to the function.
7 Press the button <PG>, the display shows the signal "PRG" which indicates that programming has been completed.
Simultaneously pressing <+> and <-> from inside a function menu allows you to return to the previous menu without making any
changes.
Simultaneously pressing <+> and <-> when the display is switched off shows the card software release.
Hold down the <+> key or the <-> key to accelerate the increase/decrease of the values.
After waiting 30s the control unit quits programming mode and switches off the display.
The tables below describe the individual functions available in the control unit.
MENU
Automatic closure time. It is activated only with "TCA"=ON logic.
TCA
At the end of the preset time, the control unit controls a closure operation.
The area covered by the gate during its partial opening movement (pedestrian)
Tped
is adjusted.
The area covered by the gate during the braking phase is adjusted.
Tsm
0 = braking disabled
PMo
The torque applied to the motor in the opening phase is adjusted.*
PMC
The torque applied to the motor in the closing phase is adjusted *.
The torque applied to the motor during braking in the closing phase is ad-
Pso
justed.*
The torque applied to the motor during braking in the opening phase is ad-
Psc
justed *
The intervention threshold of the anti-crashing device (Encoder) during the
SeaU
phase at normal speed is adjusted.*
1:maximum sensitivity - 99: minimum sensitivity
The intervention threshold of the anti-crashing device (Encoder) during braking
SEAR
is adjusted *.
1:maximum sensitivity - 99: minimum sensitivity
Activated only with SERL:ON Logic. The activation time of the service light is
TLS
adjusted.
The force of the motor brake is adjusted.
Ibra
0: disabled braking - 1:minimum braking - 99: maximum braking
An incorrect setting of these parameters may result in a danger. Comply with regulations in force!
Fuses
Programming
To access programming:
Notes:
Parameters, Logic and Special Functions
FUNCTION
* WARNING:
Settable values
MEMO
MIN-MAX-(Default)
1-240-(40s)
20-250-(50 cm)
0-250-(0 cm)
1-99-(50%)
1-99-(50%)
1-99-(50%)
1-99-(50%)
1-99-(10%)
1-99-(10%)
1-240-(60s)
0-99-(50%)