Cedar Ridge MTF4TPU Manual Del Usuario página 18

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 19).
2. Pressurize supply piping system by either
using compressed air or opening gas sup-
ply valve.
3. Check all joints from gas supply (see Fig-
ure 20 or 21) to equipment shutoff valve.
Apply a noncorrosive leak detection fluid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Equipment
Shutoff Valve
Figure 19 - Equipment Shutoff Valve
PRESSURE TESTING HEATER GAS CONNECTIONS
1. Open equipment shutoff valve (see Figure
19).
2. Open gas supply tank valve.
3. Make sure control knob of heater is in the
OFF position.
4. Check all joints from equipment shutoff
valve to control valve (see Figure 20 or
21). Apply a noncorrosive leak detection
18
All manuals and user guides at all-guides.com
INSTALLATION
Propane/LP
Supply Tank
Open
Closed
Gas Meter
5. Correct all leaks at once.
6. Light heater (see Lighting Instructions on
7. Turn off heater (see To Turn Off Gas Ap-
www.usaprocom.com
Figure 20 - Checking Gas Joints for
Propane/LP Gas
Figure 21 - Checking Gas Joints for
Natural Gas
fluid to all joints. Bubbles forming show a
leak.
page 19). Check all other internal joints
for leaks.
pliance, page 20).
Gas Valve
Equipment
Shutoff Valve
Gas Valve
Equipment
Shutoff Valve
200032-01A

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Tabla de contenido