Figure 6. Routing Heater Wires (11-22 kW)
4.
Pass the lead wires through the customer connection panel
grommet (E).
5.
Proceed to
Connecting Lead
Connecting Lead Wires
2016 and Newer Units—
See
Figure
7. Connect the lead wires to the 240 VAC Input
Sense terminals N1 and N2 as shown.
Figure 7. Input Sense Terminal Block
NOTE: It does not matter which lead wire goes into N1 or N2.
Part No. 10000003500
Rev B 07/14/17
©2017 Generac Power Systems, Inc.
All rights reserved
Specifications are subject to change without notice.
No reproduction allowed in any form without prior written
consent from Generac Power Systems, Inc.
D
E
C
002778
Wires.
002781
2013–2015 Units—
See
Figure
8. Connect the lead wires to the 240 VAC Input
Sense terminals N1 and N2 as shown.
Figure 8. Input Sense Terminal Block
NOTE: It does not matter which lead wire goes into N1 or N2.
Completing Installation
CAUTION
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.
1.
Verify all wire routings are clear of pinch points and other
damage. Use tie wraps where necessary.
2.
Install customer connection panel cover.
3.
Return the utility power supply to the transfer switch:
• In service rated transfer switches, turn the main breaker ON.
• In non-service-rated switches, turn power feeder breaker ON.
NOTE: If removed, install the T1, N1 and N2 fuses in the
transfer switch.
4.
Install controller fascia (2013–2015 units) or intake side
panel (2016 and newer units), front panel, and 7.5A DC
fuse.
5.
Complete the installation wizard programming.
6.
Move the main line circuit breaker (generator disconnect)
to ON (closed).
7.
Place the generator controller in AUTO and close lid.