Installation Procedures; Indoor Units - Carrier 40VD005L-7E-QEE Manual De Instalación Y Propietario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 104

Installation Procedures

This manual cannot completely illustrate all the properties of the purchased product. Please contact
the local Carrier distribution center if you have any questions or requests.
Please use the standard tools for the installation requirements.
Refer to the packing list, to use this series standard attached accessories of the units. Use other
accessories according to the requirements of the local installation point of our company.
1.Choose the suitable installation location. Indoor units should be installed in places with
an environment of even circulation of cool and warm blows. The following places should be
avoided:

Indoor Units

Places with high salinity (beach), high sulfurated gas(such as the thermal spring regions where copper
tubes and soft soldering are easy to erode), much mineral/cutting oil(including mechanical oil) and
steam; places where organic substance solvent is frequently used; places where machines generate
a high frequency electromagnetic wave (abnormal condition will appear in the control system); places
where high humidity exists i.e. near the door or windows (dew is easily formed); and places where the
special sprayer is frequently used.
1. The distance between the air outlet port and the ground should not be more than 2.7m.
2. Ceiling construction must be strong enough to hold the weight of the unit.
3. Make sure that the connecting pipe, the drainpipe and connecting guide line can be put into walls
to connect the outdoor units.
4. It is recommended to keep the connecting pipe between the outdoor and indoor units and the
drainpipe as short as possible.
5. If necessary, please read the attached installation instruction of outdoor units to fill the regulated
amount of refrigerant.
6. Users should check the connecting flange.
7. Electrical appliances such as television, instruments, devices, artwork, piano, wireless equipment
and other valuables should not be placed under the indoor unit to prevent condensate from
dropping into them and causing damage.
2. Dimension (unit: mm).
Model
40VD005~016L-7E-QEE
40VD018~024L-7E-QEE
a
b
c
420
892
370
850
420
1212
370
1170
d
e
f
185
640
90
185
960
90
6
g
h
i
760
152
1080
152