Installation Procedures
Installation of drain hose
Connection of indoor drain hose
1. Please use the accessory - drain hose to connect the indoor unit's water outlet and PVC pipe.
Use snap rings to tighten them, as shown in the following figure:
2. Please use rigid PVC adhesive for the connection of other pipes and ensure there is no leakage.
3. Wrap the drain hose with insulation sleeve and tighten it with a strap to prevent air leakage in
producing condensate.
4. To prevent water from flowing back into the air conditioner after it stops running, drain hose
should decline to the drainage side with a declination of above 1/100. Drain hose expansion or
water accumulation should be prevented to avoid abnormal noise.
5. The pipe connections will become loose or come off if you pull them while connecting the drain
hose . Avoid pulling out the drain hose laterally for more than 20cm. It should be supported every
0.8-1.0m to avoid bending.
6. The end of the drain hose should be more than 50mm away from the ground or the bottom of the
drainage tank. It should not be put in water. To directly drain condensate into the drainage ditch,
the drain hose must be U-shaped to avoid stink spreading through the room.
Indoor Unit
Snap ring
Water Outlet
Multiple units use water outlet header to drain water into drainage ditch.
Drainage test
Before the test, ensure the drain hose is unblocked
and all connections are tightly sealed and then
perform the drainage test as follows:
1. Inject about 500ml water into the water pan
through a water injection hole;
2. Switch on the power and make the air
conditioner operate in refrigerating mode.
Check
whether
the
water normally and there are no leakages on
connections. After the drainage test is complete,
replace the water injection hole plug. For the
position of the water injection hole,
see the figure on the right:
Drain hose PVC Drain Hose
Rigid PVC adhesive
50-100mm
<200mm
water outlet header
water
outlet
drains
Set a supporting point at every 0.8-1m.
<200mm
50-100mm
<200mm
Open or close the water injection
hole by rotating the hole plug
9
Inclination
1/100
Inclination
1/100