Panel Mount Installation
Installing the panel mount unit requires making a cutout in the panel. The cutout template is provided with
your unit or may be downloaded from www.siemens.com/processautomation.
Panel Mount Dimensions
278 mm
(10.93")
Mounting the Enclosure
Once cutout is complete and mounting holes are drilled, follow these steps:
1.
Remove lid from unit by undoing the six lid screws and lifting it off its hinges.
2.
Remove the four screws holding the motherboard to the enclosure.
3.
Be careful not to damage the electronics with static electricity. Remove the motherboard from
the enclosure by pulling the board straight out.
4.
Drill the required cable entry holes. Be sure to compensate for panel door dimensions and
make sure conduit holes do not interfere with the lower areas on the terminal block, circuit
board, or SmartLinx card.
5.
Replace board and fasten the four screws.
6.
Place the unit into the panel and insert hexagonal fasteners through bevel holes and predrilled
panel holes.
7.
Fasten with wingnuts from the rear, and hand tighten.
8.
Add conduit or glands and wire as required, then replace the lid.
Helpful hint:
Use tape to hold hexagonal heads in holes while attaching wingnuts.
7ML19985QD83
198 mm
(7.80")
MultiRanger – QUICK START MANUAL
97 mm
(3.82")
36 mm
(1.40")
Page EN-5