Quick Start Parameters
Notes:
P000 locks the unit, The unlocking value is 1954. All other values lock the unit.
Defaults are shown with an *
P001 Operation: Sets the type of measurement
required for the application.
Single Point
Primary
Model
Index
Global
0
Out-of-service
Level-how full the vessel is (MR200:
1
volume - P050)
Space-how empty the vessel is
2
(MR200: ullage - P050)
3 * Distance (transducer to material)
Values
4
DPD – dual point difference [MR200]
5
DPA – dual point average [MR200]
OCM – open channel flow rate
6
[MR200]
Pump Totalizer-total pumped vol-
7
ume [MR200]
P002: Material: Measures material type. Liquid,
may involve solids.
Single Point
Primary
Model
Index
Global
1 * Liquid or horizontal solid surface
Values
2
Solid or angled surface
P003 Maximum Process Speed: Determines
level change reaction.
Primary
Transducer
Index
1
Slow (0.1 m/min)
2 * Medium (1 m/min)
Values
3
Fast (10 m/min)
Note: Please refer to the Instruction Manual to
set up inputs, alarms and controls,
communications, and other functionality.
7ML19985QD83
P004 Transducer: Specifies transducer.
Primary
Dual Point
Index
Model
Transducer
Values
P005 Units: Specifies units used for dimensional
values.
Primary
Index
Dual Point
Values
Model
Transducer
P006 Empty: Distance in Units (P005) from
transducer face to process empty point.
Primary
Index
Values
Alters
Altered By •
P007 Span: Sets range levels to be measured.
Primary
Index
Values
MultiRanger – QUICK START MANUAL
Single Point
Dual Point Model
Model
Global
Transducer
No transducer attached (preset for
0
*
Dual Point)
1
ST-25
2
ST-50
100
STH
101
XCT-8
102
* XPS-10 (preset for Single Point Model)
103
XCT-12
104
XPS-15
112
XRS-5
250
mA input [MR200]
Global
1 * Meters
2
Centimeters
3
Millimeters
4
Feet
5
Inches
Transducer
Range: 0.000 to 99.000 m (or equiv-
alent depending on units)
Preset: 5.000 m (or equivalent
depending on units)
P007 Span
P005 Units
Level
Range: 0.000 to 99.000 m (or equiv-
alent depending on units)
Preset: based on Empty (P006)
Page EN-9