G-U BKS B-2193 Serie Manual De Instalación página 60

Cerradura con pestillo motorizada para puertas de madera y acero
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation instructions
B-2193x | B-2393x
Motor-driven shoot-bolt lock for timber and steel doors
60
Display code
Problem
Caps Error
Voltage error U
Motor does not reach
the sensor
"Locked by motor"
Critical error
EN
Cause
y
y
The voltage of the
connected
B-54903-23-3-9
emergency power
backup is no longer
sufficient
y
y
Connector of
emergency
power backup
B-54903-23-3-9
removed
y
y
Input voltage at
in
connection G2/V2
U
≤ 21.6 V DC
in
(with use of
emergency power
backup
B- 54903-23-3-9
U
≤ 22 V DC)
in
y
y
Supply voltage falls
continuously for a
period of 1 s
y
y
Break in motor wiring
y
y
Sensor defective
y
y
Test run not carried
out
y
y
Test run not
completed
successfully
y
y
Manipulation
y
y
"Locked" position
not reached 2x
consecutively
Help
y
y
Replace the
emergency power
backup
y
y
Check wiring
(see point 2.3)
y
y
Check output voltage
at power supply
y
y
Check connecting
cable (damaged?, too
long?,...)
(see point 3.1)
y
y
Check output voltage
at power supply
y
y
Check wiring.
If OK, confirm with
control signal at I1
y
y
Replace lock or have
sensor PCB replaced
y
y
Perform test run
(see point 3.2 or 6)
y
y
Open door leaf for
test run and hold open
y
y
Eliminate error as
indicated by display
code
y
y
Then repeat test run in
each case
(see point 6)
y
y
Check the lock for
foreign objects
y
y
Load on door system
too great
06.2019 | 22288S | Designed in Germany

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bks b-2393 serie

Tabla de contenido