Error Codes; Technical Data - Siemens WSx6 Serie Manual De Manejo Y De Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 83
7.

Error codes

The meter continuously runs a self-diagnosis and can thus
recognize and display various installation or meter errors:
Error code
Error
FL
nEG
Incorrect flow direction
if necessary in exchange with:
DIFF nEG
Negative temperature difference
if necessary in exchange with:
F0
No flow can be measured
F1
Interruption in the hot side temper-
ature sensor
F2
Interruption in cold side tempera-
ture sensor
F3
Electronics for temperature evalua-
tion defective
F4
Battery flat
F5
Short-circuit hot side temperature
sensor
F6
Short-circuit cold side temperature
sensor
F7
Error in the internal memory
holding
F8
Errors F1, F2, F3, F5 or F6 for
longer than 8 hours, recognition of
attempts to manipulate.
F9
Error in the electronics
8.

Technical data

Note: The information on the meter must be observed!
General
Measuring accuracy
Class 2 or 3 (EN 1434)
Environment class
A (EN 1434) for indoor installation
Mechanical class
M1 / M2 *)
Electromagnetic class
E1 *)
*) according to 2014/32/EU Directive on Measuring Instruments
Ambient humidity
< 93% rel. humidity at 25 °C, without condensation
Max. height
2000 m above sea level
Storage temperature
- 20 ... 60 °C
Electronic unit
Ambient temperature
5 ... 55 °C
Housing protection rating
IP 54 according to EN 60529
Power supply
Battery for 6 or 11 years
Operation threshold f. T
0.2 K
Temperature difference T
3 K ... 80 K
Temperature measurement
0 ... 180 °C
range
LCD
7 digit
Optical interface
Standard, EN 62056-21
Communication
Optional
Separability
Always, cable length 1.5 m
Temperature sensor
Type
Pt 500 according to EN 60751, not detachable
Connection type
Pt 500, 2 wire technology
Cable length
1.5 m
Construction type
Bolb sensor ø 5.2 × 45 mm; DS direct short,
M10 × 27,5 mm
Temperature range
0 ... 105 °C
Volume measuring unit
Protection class
IP 54 according to EN 60529; optional IP 65
Mounting place
Hot side / cold side
Installation position
Any, horizontal or vertical
Flow straightening
None
Measuring range
1:100
Temperature range
5 ... 105 °C
National type approvals may be different.
Maximum overload
qs = 2 x qp, permanent
Siemens Building Technologies
Service guidelines
Check flow or installation direc-
tion; correct if necessary
Check installation point of the
temperature sensors; exchange if
necessary
Air in the measurement unit/pipe,
bleed air from pipe (delivery
condition)
Inform service department
Inform service department
Inform service department
Inform service department
Inform service department
Inform service department
Inform service department
Measure dependent on error
code. Error message F8 must be
reset by service department.
Inform service department
A6V11285667_----_b
Nominal pressure
PN16 (1.6 MPa; PS16)
PN25 (2.5 MPa; PS25)
Power supply
Type of power supply
Battery for 6 or 11 years
Battery type
AA cell lithium
Lithium content
0.65 g per battery
Number of batteries
1 - 3; depending on the configuration
qp m³/h
Overall length and connection
0.6
110 mm (3/4 '')
1.5
110 mm (3/4 '')
130 mm (1 '')
2.5
130 mm (1 '')
Note: The documentation made available or acquired
along with our products (appliances, applications, tools
etc.) must be read carefully and completely prior to
use.
We require the users of the products and documents
to be appropriately authorized and trained and to have
appropriate specialist knowledge so that the products
can be used correctly.
Additional information about the products and applica-
tions can be found at:
 Your
nearest
www.siemens.com/bt/download or the system
supplier
Please be aware that Siemens will not be held legally
liable for any damage which results from non-
adherence to or inappropriate adherence to the points
above.
190 mm (1 '')
190 mm (1 '')
190 mm (1 '')
Siemens
location
05.06.2018
13

Publicidad

Tabla de contenido
loading

Tabla de contenido