DYNAMIC
BALANCING VALVES
ART.6544DN
Wiring
If feedback signal is not required, leave green wire detached.
(analog)
0(2)-10V modulating
Input signal
0(2)-10V DC
(digital)
2-position, Normally Closed
Open
Close
3-point floating, Normally Closed
Stop
Open
Start-Up Sequence
When power is turned on, the actuator will auto-
matically calibrate to determine closing point of
the valve. Calibration can take up to 10 minutes
depending on the valve's position at start-up.
During calibration actuator display will show
"CAL". Hereafter it will procced to normal opera-
tion mode (according to control signal).
Via Cavallera 6/A (Loc. Barco) - 25045 Castegnato (Bs) - Italy
Feedback signal
0(2)-10V DC
Power 24V AC/DC
Ground/common
Feedback signal
Power 24V AC/DC
Ground/common
Close
Feedback signal
Power 24V AC/DC
Ground/common
TIEMME Raccorderie S.p.A.
Tel +39 030 2142211 R.A. - Fax +39 030 2142206
info@tiemme.com - www.tiemme.com
EN
2-position, Normally Open
Open
Close
3-point floating, Normally Open
Stop
Close
Open
If no control signal is detected, flush is started if
enabled in the programming menu (enabled by
default), opening the valve to 5/6 of fully open.
Actuator display will show "FLUSH" until control
signal is detected.
At first start-up please enter programming menu
to set actuator settings.
ORIGINAL ITALIAN TRADEMARK