Alarm Menu

To enter the alarm menu, simultaneously press
only accessible if an alarm is present (i.e. when the icon
alarm display and press
For fast menu exit press
return to normal operation mode if no action is detected on arrow keys for 1 minute.
If the actuator is still functioning (= warning code 01, 04, 05 with failsafe and 07 with failsafe),
the
icon will blink. If the actuator is NOT functioning (=error code 01, 03, 05, 06 with failsafe
and 08), the
icon is fully on. Error codes will be shown in the information part of the actuator
display.
Display
Code
Icon
01
FULL ON
02
BLINKING
03
FULL ON
04
BLINKING
05
FULL ON
BLINKING
06
FULL ON
Via Cavallera 6/A (Loc. Barco) - 25045 Castegnato (Bs) - Italy
to go to previous.
and
simultaneously for 6 seconds. The actuator will automatically
Description
Alarm.
Enter password.
Description
Valve/actuator is overtorqued.
Actuator has reached its torque limit in
the past.
Critical - over temperature.
High temperature.
No Failsafe: Power supply not in range.
With Failsafe: Power supply not de-
tected / not in range.
Control signal not detected.
TIEMME Raccorderie S.p.A.
Tel +39 030 2142211 R.A. - Fax +39 030 2142206
info@tiemme.com - www.tiemme.com
EN
and
for 6 seconds. The alarm menu is
is displayed). Press
Action
If enabled in programming menu step 11
Disabled by default. Password: 3569266.
Details
Operation is stopped. Actuator will retry operation every
4 minutes. If over torque condition
disappear, error will convert to error code 02.
Actuator is functioning.
To reset the alarm simultaneously press
for 6 seconds.
Critical: Temperature in actuator is at least 70ºC, motor
operation is stopped. If temperature is decreasing,
operation will resume.
Actuator is still functioning. Temperature in actuator is at
least 50ºC as limited according to tech note. If tempera-
ture is decreasing, operation will resume.
Operation is stopped. Alarm will automatically reset
when voltage is back in range.
Failsafe is activated. Alarm will automatically reset
when voltage is back in range.
Operation is stopped. Alarm will automatically reset
when control signal is back in range.