DYNAMIC
BALANCING VALVES
ART.6544DN
All values selected in the programming menu are stored in non-volatile memory.
Step
Display
0
*
1
*
2
*
3
*
4
*
5
*
Via Cavallera 6/A (Loc. Barco) - 25045 Castegnato (Bs) - Italy
Programming Menu
The programming menu is always accessible. To enter the program-
ming menu, simultaneously press
bottom line in display blinks.
To change a value, press
hold down
and press
to go to previous step.
For fast menu exit press
actuator will automatically return to normal operation mode if no ac-
tion is detected on arrow keys for 1 minute.
Description
Password.
*scrolling top:
ENTER PASS WORD
Select language.
*scrolling top:
SELECT LANGUAG
Select valve model onto which the
actuator is installed.
*scrolling top:
SELECT VALVE MODEL
Choose unit scale for flow rate.
*scrolling top:
SELECT UNIT SCALE
Activate Flush mode at start-up.
*scrolling top:
SELECT FLUSH MODE
Select type of control signal.
*scrolling top:
SELECT CONTROL SIGNAL
TIEMME Raccorderie S.p.A.
Tel +39 030 2142211 R.A. - Fax +39 030 2142206
info@tiemme.com - www.tiemme.com
EN
or
or
. Press
to accept a value and go to next step
and
simultaneously for 6 seconds. The
Values
Disabled by default
Password: 3569266.
Only if Enabled (in step 11).
Change one digit at a time, press
At last digit, press
Default: English.
Possibility to choose other languages later
on (not currently an option).
Default: SM.0.0.
Select from the 10 available valve models.
Options: SM.1.1, SM.2.1...
Default: l/sec.
Options: l/sec or l/hr or GPM.
Default: Enable.
Options: Enable or Disable.
When no control signal (analog) is detected
at start up, flush mode is started (5/6 of fully
opened). It will be dismissed when control
signal is detected.
Default: 2-10VDC.
Options: 2-10VDC or 4-20mA or digital.
Choose:
• 2-10VDC for VDC
• 4-20mA for mA
• Digital for 2 position or 3 point floating.