SMA SUNNY TRIPOWER STORAGE 60 Instrucciones De Instalación página 42

Ocultar thumbs Ver también para SUNNY TRIPOWER STORAGE 60:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

9 Service
Events caused by the self-test
ID
Description
100
DC input current is negative. Sensor
fault.
264
Measurement circuit test failed.
266
Measurement circuit test failed.
272
DC surge protection device error.
Inverter will continue operation without
overvoltage protection.
273
AC grid surge protection device error.
Inverter will continue operation without
overvoltage protection.
274
Overvoltage protection device status
unknown.
350-352 Residual-current monitoring unit (RCMU)
self-test failed.
353
Current sensor test failed.
356-362 Transistor and relay test failed or inverter
relay has failed (contact assumed
welded).
366
Residual-current monitoring unit (RCMU)
self-test failed.
42
STPS60-IA-xx-13
Measure
Check the polarity of the battery. If
polarity is correct, call Service.
If the event persists, contact Service.
Warning: Do not operate the DC
load-break switch of the inverter.
Switching off the DC voltage using a
suitable DC load-break switch in the
Combiner Box is still possible. Do not
perform any further actions or switching
operations on the inverter. Contact
Service immediately.
Replace DC surge protection device.
See SPD replacement instructions for
details.
Replace AC grid surge protection
device. See SPD replacement
instructions for details.
Restart the inverter. If the event persists,
contact Service.
Contact the Service.
Contact the Service.
Warning: Do not operate the DC
load-break switch of the inverter.
Switching off the DC voltage using a
suitable DC load-break switch in the
Combiner Box is still possible. Do not
perform any further actions or switching
operations on the inverter. Contact
Service immediately.
Contact the Service.
SMA Solar Technology AG
DN
SMA Se
DC
O
rvice Lin
e
-
x
-
-
x
-
-
x
x
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
-
x
-
Installation Manual

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido