Descargar Imprimir esta página

Ecoflam MAX GAS 70 P AB Manual Del Usuario página 12

Quemadores de gas de aire soplado
Ocultar thumbs Ver también para MAX GAS 70 P AB:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 20
420010926100 Max Gas 70 - 105- 120 P AB
EN
Red blink code of
signal lamp (LED))
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
10 blinks
14 blinks
MOUNTING TO THE BOILER
TUBE DISASSEMBLY
Error code table
«AL» at
Possible cause
term. 10
on
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
on
«LP» faulty
- Loss of air pressure signal after «t10», - «LP» welded in normal position
on
Extraneous light when burner is started up
on
Time out «LP»
- «LP» welded in working position
on
Free
on
Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
on
Free
on
Free
off
Wiring error or internal error, output contacts, other faults.
on
CPI contact not closed
12

Publicidad

loading

Este manual también es adecuado para:

Max gas 105 p abMax gas 120 p ab