CONCENTRIC FLUE PIPE INSTALLATION
Concentric flue pipe
Fit the concentric elbow pipe in the position required and insert the sealing gasket. Fit the appropriate
diaphragm (see table below).
Fit the air intake and flue pipes, observing the distances indicated on the installation scheme. The flue pipe
should slope slightly outward.
CONCENTRIC FLUE PIPE
Ø100
Max. 3000
450
DOUBLE FLUE PIPE
ATTENTION: Use only air intake/ fumes evacuation kit produced by Lamborghini Caloreclima.
All manuals and user guides at all-guides.com
240
100
Max. 3000
250
CONCENTRIC
FLUE PIPE
Length. 1 m
Diaphragm Ø 77 mm
NOTE: Maximum length of concentrical flue pipe is 3 m.
Maximum length of separate flue pipe (Inlet + Exhaust) is 16,5 m.
Installing an elbow to connect the boiler to the chimney will cause a
drop in pressure. The values set out in the table below indicate the
necessary modifications to the length of the linear pipes.
INSTALLATION
TYPE
CONCENTRICAL
FLUE PIPE
SEPARATE
INTAKE/EXHAUST
360
CONCENTRIC
FLUE PIPE
Lenght. 3 m
Diaphragm Ø 82 mm
(standard)
90° ELBOW
FITTING
1 m
0,6 m
45
FLUE
ELBOW
PIPE
Air
diaphragm
DOUBLE
PIPE
Diaphragm Ø 82 mm
(standard)
45° ELBOW
FITTING
0,5 m
0,3 m