Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Page 2
Provide each unit with a single-phase power supply from a 120 V through 347 V circuit used for normal lighting. The PEL option
provides an additional switched input connection. If Switched Hot input is connected to a live wire, the lamps will always be
illuminated, otherwise the Lamps will illuminate as a function of the photosensor.
PRODUCT DAMAGE WILL OCCUR IF THE RATED INPUT VOLTAGE IS EXCEEDED.
NOTE: The battery must be connected to the charger board prior to applying AC power to the unit. Battery damage may occur if the
battery is connected longer than 24 hours without continuous AC power provided. See also "Important Battery Information", page 4.
NOTE To meet the minimum illumination requirements of NFPA 101 (current Life Safety Code), the maximum mounting height from
ground is 11.3 feet
This unit should be mounted ONLY through a pair of the preformed keyholes onto a 4" "OCTAGON" junction box, or
NOTE:
through a pair of the keyhole knockouts onto a 4" "SQUARE" junction box or using conduit entry.

OPENING THE UNIT

Use a flat head screwdriver, locate the
slots, one on each side and two on top,
and twist screwdriver in each slot.
JUNCTION BOX MOUNTING
-Images shown below may vary from actual product-
Feed the supply leads through
1
the junction box and prepare the
lead ends to make connections
to the fixture leads.
Ground
wire
4
Mount the rear housing on the junction box with suitable hardware (not supplied).
AFFINITY
INSTALLATION and WIRING
On the rear housing, remove the
2
round center knockout (1.2"
diameter) and the desired pair of
keyhole knockouts. Use
knockouts instead of drilling
holes to prevent metal shavings
from entering the unit.
The unit as shipped is designed to
be mounted on a smooth rigid
surface to allow foam pad to tightly
seal. If mounted to other surface,
the installer should apply silicone to
the top and sides of the unit to seal
and prevent water ingress from the
back of the unit.
Round
knockout
®
LIFE SAFETY SOLUTIONS
TEL: 800-705-SERV (7378)
techsupport-emergency@acuitybrands.com
Top housing
slots
Junction boxes accommodated:
4" Square
4" Octagon
3-1/2" Round or Octagon
Single Gang Box
www.lithonia.com
Route the supply leads through
3
the knockout and attach them to
the respective leads on the
fixture. Attach the incoming
ground wire to the unit ground
wire.
© 2020, Acuity Brand Lighting,Inc.
912-00020-001
Rev. D, 3/2021
All Rights Reserved.