3. Operations
EN
01: Output voltage setting
Interface
02: Output Frequency
Interface
60 Hz, CVCF mode
50 Hz, Normal mode
Interface
03: Voltage range for bypass
61
PH 9280 | PH 9290
Uninterruptable Power Supply
Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac
Setting
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three options in parameter 2:
50.0Hz: The output frequency is setting for 50.0Hz.
60.0Hz: The output frequency is setting for 60.0Hz.
ATO: If selected, output frequency will be decided according to the latest normal utility
frequency. If it is from 46Hz to 54Hz, the output frequency will be 50.0Hz. If it is from
56Hz to 64Hz, the output frequency will be 60.0Hz. ATO is default setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You may choose following
two options in parameter 3:
CF: Setting UPS to CVCF mode. If selected, the output frequency will be fixed at 50Hz
or 60Hz according to setting in parameter 2. The input frequency could be from 46Hz
to 64Hz.
NCF: Setting UPS to normal mode (not CVCF mode). If selected, the output frequency
will synchronize with the input frequency within 46~54 Hz at 50Hz or within 56~64 Hz
at 60Hz according to setting in parameter 2. If 50 Hz selected in parameter 2, UPS will
transfer to battery mode when input frequency is not within 46~54 Hz. If 60Hz selected
in parameter 2, UPS will transfer to battery mode when input frequency is not within
56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will show the current frequency.
Setting
Parameter 2: Set the acceptable low voltage for bypass. Setting range is from 110V to
209V and the default value is 110V.
Parameter 3: Set the acceptable high voltage for bypass. Setting range is from 231V
to 276V and the default value is 264V.