11: Shutdown point for programmable output
Interface
12: Hot standby function enable/disable
Interface
13: Battery voltage adjustment
Interface
Segurança e harmonia
ININTERRUPTA
Setting
Parameter 2: 001.
Set shutdown time for programmable output.
Parameter 3: Shutdown time in minutes.
Setting range is from 0 to 300. When shutdown time arrives, the programmable output
terminal will be cut off. The default value is 30 minutes.
Parameter 2: 002
Set shutdown voltage for programmable output.
Parameter 3: Shutdown voltage in V.
Setting range is from 11.2 to 13.6. If the battery voltage is less than the setting point,
the programmable output will be cut off. The default value is 11.2V.
Setting
When input neutral line is correctly detected, "RES" will be displayed in parameter 2
and parameter 3.
When a loss of input Neutral line is detected, this program will become "input Neutral
line detecting" menu. It will display "N.L" in parameter 2 and "CHE" in parameter 3.
When it occurs, please re-connect the input Neutral line well. Then, press the "Enter"
key to activate input Neutral line detecting. If it's connected well and correctly detected,
it will show "RES" in parameter 2 and parameter 3 when entering the setting menu next
time.
Setting
Parameter 2: Select "Add" or "Sub" function to adjust battery voltage to real figure.
Parameter 3: the voltage range is from 0V to 5.7V, the default value is 0V.