Parker Hiross Hyperchill-Plus ICEP040 Manual De Uso página 16

Ocultar thumbs Ver también para Hyperchill-Plus ICEP040:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 19
English
4.6 Setting clock/date.
(see fi g. 1/3)
1. Press the buttons "
" "
", together to enter in the menu
"FrEE".
set
2. Press the button "
" to enter in the menu "Ai".
3. Press the button "
" to enter in the il menu "CL".
set
4. Press the button "
" to enter and visualize the parameter
"HOUr".
set
5. Press the button "
" until the fl ashes of the parameter "HOUr".
6. Select the fl ashing parameter "HOUr"/"dAtE"/"4EAr" using the
set
button "
" and press "
" to enter.
7. Change the fl ashing value using the buttons "
set
and down) and press the button "
" to confi rm.
esc
8. Press the button "
" to return to the menu "FrEE".
9. Press the buttons "
" "
" together to exit.
Fig.3
set
dr4
FrEE
Ai
FrEE
esc
4EAr
dAtE
set
set
18.20
01.09
2015
set
!
The memory of the "clock / date" has a maximum duration of
three days, so if the controller is left without power for more than
three days, the data set hour / month / year are lost.
Adjust the clock at the start up of the machine, and whenever
necessary.
4.7 Visualization of temperature probes B1,B2
(see fi g.1/4)
Fig.4
b1
1. Turn the main swicth (QS) to "ON" and wait for the "OFF" visualiza-
"and "
" (up
tion.
set
2. Press the button "
3. The display shows the temperature of the probe B1.
4. Using "
"and "
seconds to see the temperature value.
esc
5. Press the button "
4.8 Alarms management
CL
(see fi g.1/5)
Fig.5
set
ALARM
HOUr
set
3 sec.
HOUr
set
17.15
set
1. Press the button "
!
2.
Alarm ON (led on: red).
set
3. Press the button "
buttons select the parameter " AL" .
ICEP040-060
set
12.5
b2
3
sec.
5.0
" to start up.
" buttons select the probe (B2), wait for 3
" to exit
set
!
23.5
set
Pb
AL
set
Er__
Er__
" to start up.
" to enter in the menu, using "
"and "
set
4. Press the button "
" to see the alarm code.
5. Press the button "
" to see the next code.
esc
6. Press the button "
" to exit
4.8.1
Analog /Digital input alarms
CODICE
DESCRIZIONE
Er01
Sensor B1 cutout or broken
Er02
Sensor B2 cutout or broken
Er03
Sensor B3 cutout or broken
Er04
High pressure
Er05
Low pressure
Er06
Pump thermal cutout
Er07
Low water level
High pressure trasducer cutout or
Er08
broken
Er10
Sensor B4 cutout or broken
Er12
Compressor thermal *
Er14
High temperature sensor B1
Er15
Low temperature sensor B1
Er16
High temperature sensor B2
Er17
Low temperature sensor B2
Er18
High temperature sensor B3
Er19
Low temperature sensor B3
Er20
Antifreeze
Er21
Exceeded compressor working hours
Er23
Phase monitor
Er24
Exceeded unit working hours
Er25
Communication expansion
Er26
Controller memory
!
*
(Only oil model)
If the evaporator temperature falls below 5°C for more than 120s
then an alarm "
Er12
" will occur, blocking the unit.
!
esc
Press the button "
" to reset alarms (5sec).
"
6 / 8
AZIONE RESET
Alarm
A
Alarm
A
Alarm
A
Alarm
M
Alarm
M
Alarm
M
Alarm
M
Alarm
A
War-
M
ning
Alarm
M
Alarm
A
Alarm
A
Alarm
A
Alarm
A
Alarm
A
Alarm
A
Alarm
A
War-
A
ning
Alarm
M
War-
A
ning
Alarm
A
War-
A
ning

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hyperchill-plus icep050Hyperchill-plus icep060

Tabla de contenido