CONFIGURATION.
By mean of
we can change the values and press ENTER for validation. Whenever we want to quit the
configuration sequence press MENU. After every ENTER it will appear automatically the different screens that
constitute the sequence of configuration.
P LINE
SET P
0. To start configuration sequence push MENU during 3".
0,0 bar
0,0 bar
1.By mean of keys
LANGUAGE
ENGLISH
"LANGUE FRANÇAISE", "LINGUA ITALIANA" e "IDIOMA ESPAÑOL".
2. By mean of keys
MAX. INT. PUMP 1
OFF
the thermal protection. This value is located over the characteristics plate of the
motor. Press ENTER for validation.
3. Follow instructions of the previous step. See intensity value in A over the
MAX. INT. PUMP 2
OFF
characteristics plate.
4. Using
MIN. SPEED
30 Hz
pump´s motor.The default value is 30 Herz .
5. If the installation does not have level probe press ENTER to validate NOT. If
LEVEL PROBE
NO
the installation has a level probe, by mean of keys
YES.
6. Being inside configuration menu we are having access to the phase of
PROGRAMMING MENU
programming.
7. This will be the system working pressure. Use keys
SET PRESSURE
2,0 bar
value (2 bar). WARNING ! SET pressure must be under 12 bar.
8.The default value is 0,3 bar. This value of pressure is the one that the system
DIF. START
0,3 bar
will subtract to the input pressure, resulting the final pressure to which the
system will SET ALT in motion when the hydraulic network have a demand.
Using keys
value between 0,3 and 0,6 bar. Example:
The value should be greater as much as smaller be the accumulation and vice
versa.
9. There are 2 view modes to choose::
VIEW MODE
PRESSURE
- Pressure: it is visualized "P LINE" (real pressure of the installation) and "SET P"
(working programmed pressure).
- Service: it is visualized "Hz" (working frequency of the inverter), "LINE" (input
pressure chosen), "SET P" (real pressure of the installation)
10. After pressing ENTER pushbutton, the system will remain configured showing
P LINE
SET P.
0,0 bar
0,0 bar
the type of view chosen in the previous section.
Hz
LINE
SET P.
42
2,0 bar 2,0
Press AUTOMATIC in order to quit manual mode.
we can choose the languages: "LANGUAGE ENGLISH",
enter the nominal intensity value in A of pump 1 enabling
we can increase the lower limit of the speed of rotation of the main
to modify the initial value. It is recommended to maintain this
- Input pressure:
- Differential start:
- Final start pressure:
we can change NO by
for modify the initial
2
bar.
0,3 bar.
2 - 0,3 = 1,7 bar.
MENU
3"
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
AUTOMATIC