Do not exceed the rated output of the generator.
Figure 3 - Control Panel
14
15
16
17
18
PRE-USE CHECK
Prior to starting the generator and adding loads, perform the
following tasks:
1. Make sure the generator in on a firm, level, non-combustible
surface with at least five (5) feet of clearance on all sides.
Never operate in an enclosed area or
indoors! NEVER use in the home, or in
partly enclosed areas such as garages,
even if doors and windows are open! ONLY
use outdoors and far from open windows,
doors, vents, and in an area that will not
accumulate deadly exhaust.
2. Remove the fuel cap and check the fuel level. If fuel is needed,
see the section "FUELING THE GENERATOR".
3. Remove the left side service cover and check the oil level
by removing the oil filler cap. The oil level should be to the
bottom of the threads on the oil fill pipe. If oil is needed, see
the section "ADDING ENGINE OIL".
NOTE:
19 20
21
4. Replace and secure the left side service cover.
5. Make sure there are no loads connected to the generator.
6. The National Electric Code (NEC) requires the frame and
external electrically conductive parts of the generator be
properly connected to an approved earth ground. Proper
grounding of the generator will prevent electrical shock in
the event of a ground fault condition in the generator or in
connected electrical devices. Proper grounding also helps
dissipate static electricity, which often builds up in unguarded
devices.
7. Local electrical codes may also require proper grounding of
the generator.
Starting the generator with accessories
connected to the 120 VAC outlets will damage
the generator and the connected accessories.
STARTING THE GENERATOR
Once the fuel and oil levels have been checked and it has been
verified there are no loads connected, the generator may be
started. Turn the FlexPower Switch OFF (O).
1. Open the fuel valve (Figure 4), located below the starter rope
pull, by turning to the valve 90° counter-clockwise to the "ON"
(I) position.
Figure 4 - Fuel Valve
TURNING THE FUEL ON
2. Pull up on the center of the fuel fill cap and prime the fuel
system by depressing the plunger up to five (5) times with the
vent closed (Figure 5 on next page).
3. Open the fuel tank vent on the top of the fuel fill cap by turning
the center portion to the "ON" mark (Figure 6 on next page).
4. If the engine is cold or has not been run for some time, engage
the choke by pushing the choke lever to the right.
5. Grip the handle for the pull starter and brace your other hand
against the generator. Pull the rope slowly until resistance is
felt, then pull the rope rapidly.
6. If the engine does not start, repeat steps 2-5 until the engine
fires and begins to run.
Operation
5 5