Descargar Imprimir esta página

Publicidad

Idiomas disponibles

Idiomas disponibles

Using Test Leads

Follow all safety procedures, wear proper PPE in accordance to NFPA 70E and
follow the guidelines below and the instructions in this manual when operating
the meter with TL-757 Test Leads or equivalent. Test Leads must be rated for the
electrical environment the meter is being used in and have a voltage rating of at
least the voltage of the circuit to be measured. Failure to comply can result in
serious injury or death.
Choking Hazard, Small Parts. Keep Away from
Children. Sharp Objects Hazard, This is not a toy. It is not for use or play by
children. Keep Away from Children. Failure to do so can result in serious
injury.
1. Use only approved test leads. Do not use improvised connections that could
present a safety hazard.
2. Never measure AC or DC current while the test leads are inserted into the input
jacks.
3. Prior to using the test leads, inspect them carefully for damaged insulation,
exposed metal or bent probes. Check test leads for continuity. Do not use leads
if they appear damaged.
4. When using the probes, keep fingers behind the finger guards on the probes.
5. Connect the common test lead before connecting the live test lead. When
disconnecting test leads, disconnect the live test lead first.
6. Always ensure that test leads are secured so that they cannot be accidentally
snagged or tripped over.
This meter is intended for use with the IDEAL TL-757 lead set (provided with this
product) or equivalent. The lead set must comply with requirements for Overvoltage
and Measurement Categories CAT IV 600V CAT II 1000V.
WARNING: Arc Flash and Shock Hazard, Proper PPE Required.
WARNING:
.....
12

Publicidad

loading

Este manual también es adecuado para:

61-405 fork meters