(2) If the self-diagnostics function fails to operate
Check the indoor unit.
Is the fuse blown?
Replace the controller.

8-3. Checking the Indoor and Outdoor Units

(1) Checking the indoor unit
No.
Control
1
Use the remote controller to operate the
unit in "TEST run" mode. To determine
whether the mode is currently in
"TEST run" mode, check the 4 indicator
lamps on the unit. If all 4 are blinking,
the current mode is "TEST run."
If there are no problems with the above, then check the outdoor unit.
For the "Test run" procedure, refer to 5. "HOW TO TEST RUN THE AIR CONDITIONER" on Appendix C.
(2) Checking the outdoor unit
No.
Control
1
Apply the rated voltage between outdoor
unit terminals L and N.
2
Short-circuit the outdoor unit COM terminal
to the T-RUN terminal.
If there are no problems with the above, then check the indoor unit.
Using the TEST/T-RUN terminals
T-RUN
: Test run (compressor and fan motor turn ON).
TEST/MV : Compresses time to 1/60th (accelerates
operation by 60 times faster than normal).
(3) Checking the serial communications
Control 1
Initial self-diagnostics
Timer
Operation
• • •
• •
(3)
(2)
(1)
Turn the power OFF before performing short circuiting procedures.
Refer to the previous pages when performing system self-diagnostics.
So that the check can be made quickly, indicators blink at first communication after power ON.
Before performing the above checks, perform "TEST run" operation, and check that the rated voltage is output to terminals L and N
on the outdoor unit. If it is not output, there is a failure related to the indoor unit power.
All manuals and user guides at all-guides.com
Normal
The rated voltage must be present between inter-unit wirings 1 and 2.
Connect a 5 k ohm resistor between inter-unit wirings 2 and 3. When the
voltage at both ends is measured, approximately 12 to 15V DC must
be output and the multimeter pointer must bounce once every 8
seconds.
Or instead of measuring the voltage, you can insert an LED jig and
check that the LED flickers once every 8 seconds.
The control panel LED (red) must illuminate.
The compressor, fan motor, and 4-way valve must all turn on.
Control 2
Short-circuit terminals 2 and 3 on
Short-circuit terminals 2 and 3 on
the outdoor unit terminal plate.
the indoor unit terminal plate.
Timer
Operation
• • •
• •
(3)
(2)
(1)
No indicators illuminate and the
indoor fan does not rotate.
Check the power voltage.
Blown
Replace the circuit
board or the fuse.
Check items (unit operation)
Check items (unit operation)
.... OFF
Probable location of malfunction
Timer
Operation
• • •
• •
(3)
(2)
(1)
Indoor unit circuit board failure
Outdoor unit circuit board failure
Failure (open circuit, contact failure, etc.)
in the inter-unit wirings
Outdoor unit circuit board failure
32
TEST/T-RUN terminals
(TEST)/MV T-RUN
COM
.... Blinking
.... Illuminated