LPG kit
2.1

Kit description

The kit allows the burners RS 50, RS 50/M and RS 50/E de-
signed to work with natural gas to burn LPG.
The kit is composed of:
Description
Distributor assembly
Plug
Fixing screws for plug
Label
Instruction
2.2

Technical features

Burner
Burner output
Minimum gas pressure
Fuel
2.3
Conversion
Proceed as follows:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
 replace the distributor unit 1)(Fig. 1) with the one for LPG
operation supplied with the standard equipment;
 remove the central pipe 2);
 replace the ring nut 3) with the plug 4)(Fig. 1) supplied with
the standard equipment.
20023574
Quantity
1
1
2
1
1
RS 50 - RS 50/M - RS 50/E
80 - 630 kW
68.800 - 514.800 Mcal/h
Maximum capacity requires 22.4 mbar measured on the pipe coupling, with 0 mbar resistance in the
combustion chamber and gas with net calorific value of 22.200 kcal/Nm
Commercial LPG (C
H
= 93 - 94%)
3
8
Net calorific value = 25.8 kWh/Nm
LPG kit
Apply the self-adhesive label for LPG operation
near the characteristics label.
WARNING
Before starting the kit installation operations, get a
suitable lifting system ready.
Be careful as some drops of fuel may leak out dur-
ing the kit installation phase.
Tab. A
3
3
- 22.200 kcal/Nm
D10227
3
2
GB
3
D10228
4
Tab. B
1
2
Fig. 1