2
LPG kit
2.1
Kit description
The kit allows the burners RS 50, RS 50/M and RS 50/E de-
signed to work with natural gas to burn LPG.
The kit is composed of:
Description
Distributor assembly
Plug
Fixing screws for plug
Label
Instruction
2.2
Technical features
Burner
Burner output
Minimum gas pressure
Fuel
2.3
Conversion
Proceed as follows:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
replace the distributor unit 1)(Fig. 1) with the one for LPG
operation supplied with the standard equipment;
remove the central pipe 2);
replace the ring nut 3) with the plug 4)(Fig. 1) supplied with
the standard equipment.
20023574
Quantity
1
1
2
1
1
RS 50 - RS 50/M - RS 50/E
80 - 630 kW
68.800 - 514.800 Mcal/h
Maximum capacity requires 22.4 mbar measured on the pipe coupling, with 0 mbar resistance in the
combustion chamber and gas with net calorific value of 22.200 kcal/Nm
Commercial LPG (C
H
= 93 - 94%)
3
8
Net calorific value = 25.8 kWh/Nm
LPG kit
Apply the self-adhesive label for LPG operation
near the characteristics label.
WARNING
Before starting the kit installation operations, get a
suitable lifting system ready.
Be careful as some drops of fuel may leak out dur-
ing the kit installation phase.
Tab. A
3
3
- 22.200 kcal/Nm
D10227
3
2
GB
3
D10228
4
Tab. B
1
2
Fig. 1