Heronhill - for all your Toshiba requirements
Unit Installation – CH/CHR/C Units
Before Installation
1
Take off the accessories.
Side
panel
(left)
2
Remove
the hanger
Body
(left, right).
3
Remove all the
metal shipping fix-
tures (left corner,
centre, right cor-
ner).
4
Remove the side panels by hand.
Slide them in order of 1 - 2 .
Shipping fixture
(centre)
Detail figure of the hinge
portion
Hinge
Body
Installing Ø 10 Hanging Bolts
Ø Hanging Bolts are procured locally
G
Install hanging bolts at the spacings shown below.
INNER HANGING
Hole for hanging bolt
(4 – 12 x 27 slots)
Hanging bolt pitch
Bmm (Hanging bolt pitch)
Amm
Model (RAV-)
Amm
134CH/CHR/C
1030
164CH/CHR/C
1030
264CH/CHR/C
1230
364CH/CHR/C
1430
464CH/CHR/C
1630
Tel: 01823 665660
All manuals and user guides at all-guides.com
I
U
L
NDOOR
NIT
The positions of the hanging bolts are printed on the carton
box. (The size is not printed.)
Inlet grille
G
Securely fix left
and right side panels
with a screw
supplied after unit
installation.
Side panel
Installing method of the Hanging Bolt
(right)
10-20mm
5
Pull the air filter
out then remove
the inlet grille fixing
screws.
Installing Hexagon Bolt
To remove the
inlet grille take the
hinge portion off in
order of 1 - 2 .
Determining installation position and direction
of the piping and wiring
BACK VIEW
OUTER HANGING
Hole for hanging bolt
(4 – 12 x 27 slots)
Hanging bolt pitch
Cmm (Hanging bolt pitch)
Amm
Bmm
Cmm
Opening Knock Out Hole
920
1020
920
1020
1120
1220
In case of
1320
1420
right or left
1520
1620
attachment
~ 13 ~
~ 13 ~
www.heronhill.co.uk
OCATION
Position of hanging bolt
(ø10 printed)
Bmm (inner hanging)
Cmm (outer hanging)
Wooden-strutted room
Install hanging bolts on a square
wooden piece placed over beams.
Newly-built concrete slab
Install hanging bolts with
inserts, embedded bolts, etc.
Wooden
Beam
piece
Hanging
bolt
Edge
(sharp
insert)
(accessory)
M8 x 25mm hexagon bolts (4)
Knock out
(rear attachment)
Drain connection
(OD 20mm)
Liquid line connection
Gas line connection
TOP VIEW
Slit
Fax: 01823 665807
G
The dotted
line indicates
the rear end
of the unit. To
be detached
on the dotted
line.
Reinforcing bar
Embedded
bolt
(Slide
Embedded bolt
insert)
of piping
Allow a spacing of
about 10mm
SIDE VIEW
Knock out
(right or left attach-
ment)
Cut the slit
portion by a
saw or knife
GB