Descargar Imprimir esta página

Heat Insulation - Toshiba RAV-104NH Instrucciones De Instalación

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 116
Additional Refrigerant
The amount of refrigerant put into the outdoor unit at the factory is sufficient to fill up to 20m of
!
refrigerant pipework.
If the length of the refrigerant pipework is 20m or less, addition of refrigerant at the installation site
!
is unnecessary.
If the length of the pipework exceeds 20m, extra refrigerant must be added. Refer to the table
!
below for details of the extra amounts.
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of
!
the compressor.
The prescribed amount of the replenishment of the refrigerant is shown in the table below:
MODEL
(RAV-)
GB
134AH-PE
164AH-PE
264AH/AH8-PE
364AH8-PE
464AH8-PE
134A-PE
164A-PE
264A/A8-PE
364A8-PE
464A8-PE

Heat Insulation

Provide heat insulation on the refrigerant piping on both the liquid side and gas side separately,
!
and ensure that all joints in the insulation are vapour sealed.
Since the temperature of the piping on the gas side increases during heating operations, the heat
!
insulating material used must be able to withstand temperatures of more than 120
Use the pipe insulation supplied in the accessory pack to insulate the piping connecting section on
!
the indoor unit side.
Pressure Measurement
Connect the pressure gauge to the locations in the table below when measuring the pressure dur-
!
ing operation.
!
A gauge is required since check joints are used for the connecting sections.
During cooling
During heating
Note: During cooling operation, the pressure in the packed valve on the liquid side reduces.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
All manuals and user guides at all-guides.com
R
EFRIGERANT
Additional amount of refrigerant to add at
±
installation site (kg)
50g
Less
Less
Less
Less
Less
than
than
than
than
than
20m
25m
30m
35m
40m
0.18
0.35
0.18
0.35
0.18
0.35
0.18
0.35
0.53
0.7
0.25
0.5
0.75
1.0
0.18
0.35
0.18
0.35
0.18
0.35
0.18
0.35
0.53
0.7
0.25
0.5
0.75
1.0
!
ADD ONLY R407C REFRIGERANT TO THESE UNITS
High-pressure side
Check joint in the outdoor unit
Gas side packed valve
www.heronhill.co.uk
P
IPING
Recharge amount if unit is reclaimed
Less
Less
Less
Less
Less
than
than
than
than
than
45m
50m
5m
20m
25m
0.79
1.05
1.23
0.94
1.2
1.38
1.64
1.9
2.08
0.88
1.05
2.44
2.7
2.88
1.25
1.5
3.13
3.5
3.75
0.79
1.05
1.23
0.94
1.2
1.38
1.64
1.9
2.08
0.88
1.05
2.44
2.7
2.88
1.25
1.5
3.13
3.5
3.75
Low-pressure side
Gas side packed valve
Check joint in outdoor unit
~ 28 ~
±
(kg)
50g
Less
Less
Less
Less
Less
than
than
than
than
than
30m
35m
40m
45m
50m
1.4
1.55
2.25
3.05
3.23
3.4
3.58
3.75
4.0
4.25
4.5
4.75
5.0
1.4
1.55
2.25
3.05
3.23
3.4
3.58
3.75
4.0
4.25
4.5
4.75
5.0
˚
C –
HEAT PUMP TYPES ONLY.
Fax: 01823 665807

Publicidad

loading