Concealed Duct High Static Pressure
Procedure example 1
Manual address setup procedure
While the operation stops, change the setup.
(Be sure to stop the operation of the unit.)
3
-2,
4
-2,
5
-2
7
1
1
Procedure
Push simultaneously
+
+
more. After a while, the display part flashes as shown below.
Check the displayed CODE No. is [10].
• When the CODE No. is other than [10], push
erase the display and repeat procedure from the first step.
(After pushing
button, operation of the remote
controller is not accepted for approx. 1 minute.)
(For a group control, No. of the firstly displayed indoor unit
becomes the header unit.)
(* Display changes according to
the model No. of indoor unit.)
2
Procedure
Every pushing
button, the indoor UNIT No. in the
group control is displayed in order. Select the indoor unit of
which setup is changed.
In this time, the position of the indoor unit of which setup is
changed can be confirmed because fan of the selected
indoor unit operate.
3
Procedure
1. Using TEMP.
/
buttons, specify CODE No.
[12].
(CODE No. [12]: Line address)
2. Using TIME
/
buttons, change the line address
from [3] to [2].
All manuals and user guides at all-guides.com
7
3
-1,
4
-1,
5
-1,
6
3
-3,
4
-3,
5
-3,
2,6
buttons for 4 seconds or
button to
– 32 –
3. Push
button.
In this time, the setup finishes when the display changes
from flashing to lighting.
Indoor unit No. before setup change is displayed.
4
Procedure
1. Using TEMP.
/
buttons, specify CODE No.
[13].
(CODE No. [13]: Indoor address)
2. Using TIME
/
buttons, change the indoor
address from [3] to [2].
3. Push
button.
In this time, the setup finishes when the display changes
from flashing to lighting.
Indoor unit No. before setup change is displayed.
5
Procedure
1. Using TEMP.
/
buttons, specify CODE No.
[14].
(CODE No. [14]: Group address)
2. Using TIME
/
buttons, change the SET DATA
from [0001] to [0002].
(SET DATA [Header unit: 0001] [Follower unit: 0002])
3. Push
button.
In this time, the setup finishes when the display changes
from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
Installation Manual
EN
32-EN