• Output parameters
O u
Output settings
Number of outputs
Alarm type 1
Value
(absolute only)
0
Alarm type 2
1
2
3
4
5
Alarm type 3
6
7
+8 to disable on power-up until first alarm
+16 to memorize
+32 to filter with F.O. mode (output filter mode)
Output filter mode
delay for F.O.
Minimum output pulse
Disabled by setting value 0
Displayed if associated with at least one output
Fault action (in case of
damaged sensor)
Er, br, Eb
• Protection
P r
Protection code
+4 to disable In and Ou pages
+8 to disable Cf page
+16 to enable maintenance of reset latch at power-off (for linear inputs only)
+32 base configuration (the following parameters will not be displayed:
In: Ft, Fd, Of, L_L, H_L
Ou: On [forced to no. outputs present], rE)
Ft, Fd, Of remain at set value
L.L, H.L are forced to L.S, H.S
0 to 3
1. t - 2. t - 3. t
Direct
Absolute or
Normal or
(high limit)
Relative
Symmetric
Inverse
to previous
(window)
(low limit)
absolute
Direct
Absolute
Normal
Inverse
Absolute
Normal
Direct
Relative
Normal
Inverse
Relative
Normal
Direct
Absolute
Symmetrical
Inverse
Absolute
Symmetrical
Direct
Relative
Symmetrical
Inverse
Relative
Symmetrical
0 not active: calculated status
is sent directly to relay
1 On delay (DON)
2 On delay after it has
been turned off (DBI)
3 Off delay (DOF)
4 Delay for activation only
at power-up (DPO)
+ 8 time base max. 99 min (default = 99 sec)
0 to 99 min or sec
0 to 99 sec
Value Output 1 Output 2 Output 3
0
OFF
OFF
OFF
1
ON
OFF
OFF
2
OFF
ON
OFF
3
ON
ON
OFF
4
OFF
OFF
ON
5
ON
OFF
ON
6
OFF
ON
ON
7
ON
ON
ON
Value
Displayed
Modifiable
parameters
parameters
0
o.1, o.2, o.3
o.1, o.2, o.3
1
o.1, o.2
o.1, o.2
2
o.1
o.1
3
o.1
none
• Custom linearization
Custom linearization of
L n
main input
Step 0
(beginning of scale value)
.......
∆
Step 32
(end of scale value)
Step 33
Step 34
Step 35
(*) only for CPU, TC_LIN and tP = TC CUSTOM
• User calibration
U.C.
CPU T Function
U. C.
1
analog retransmission
2
Custom RTD sensor
3
Custom PTC sensor
4
Custom NTC sensor
5
Potentiometer (0 to 1V)
Calibration of
minimum (*)
Calibration of
maximum (*)
14
Display limits
(-1999 to 9999 for 4 digit display)
the n step value corresponds to input:
∆
mV beginning scale + n *
mV
mV = (mV full scale - mV beginning scale) / 32
Display limits
(-1999 to 9999 for 4 digit display)
mV beginning
of scale
mV end of scale
mV at 50°C
output
∆ ∇
(*) when U.C. = 1 press keys
analog output
(*)
(*)
(*)
to calibrate