General Prerequisites For Operating The Devices - Festo EduTrainer 8071407 Instrucciones De Utilizacion

Minicontroladores
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Mini Control Systems EduTrainer

1 General prerequisites for operating the devices

General requirements for safe operation of the devices:
National regulations for operating electrical systems and equipment must be observed in commercial
facilities.
The laboratory or classroom must be overseen by a supervisor.
A supervisor is a qualified electrician or a person who has received appropriate instruction,
has knowledge of the respective safety requirements and safety regulations and
whose training has been documented accordingly.
The laboratory or the classroom must be equipped with the following devices:
An emergency-off device must be provided.
At least one emergency-off device must be located within, and one outside the laboratory or
the classroom.
The laboratory or classroom must be secured so that the operating voltage and compressed air supply
cannot be activated by any unauthorised persons, for example by means of:
A key switch
A lockable on-off valve
The laboratory or classroom must be protected by residual current devices (RCDs).
Electrical devices (e.g. power supply units, compressors and hydraulic power units) may
only be operated in training rooms which are equipped with residual current devices (RCDs).
Type B residual current circuit breakers with a residual current rating of ≤ 30 mA.
The laboratory or classroom must be protected by overcurrent protection devices.
Fuses or circuit breakers
No damaged or defective devices may be used.
Damaged devices must be barred from further use and removed from the laboratory or classroom.
Damaged laboratory cables, pneumatic plastic tubings and hydraulic hose lines are a
safety hazard and must be removed from the laboratory or classroom.
24
®
© Festo Didactic 8071396

Publicidad

Tabla de contenido
loading

Tabla de contenido