Intended Application - HEROSE 06401 Instrucciones De Servicio

Válvula inversora
Ocultar thumbs Ver también para 06401:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 31
4.3

Intended application

Changeover valve for the installation of two safety valves in a possible combination with bursting discs for
protecting gas storage tanks. The requirements of the pressure equipment directive for redundant or
different types of safety devices are fulfilled with this valve and in combination with safety valves with the
same setting pressure. Additional connections are available for suitable means of testing.
In the case of servicing the safety valves or replacement of the bursting discs, the side to be serviced is
isolated from the vessel.
In the end position one outlet is open and the other is closed. It is not possible to shut off both outlets at
the same time.
4.4
Operational data
Valve
06401
06405
06406
4.5
Media
Gases, cryogenic liquefied gases and their gas mixtures, such as:
Valve
06401
06405
06406
Operating instructions
Nominal
Temperature
pressure
PN 16 – PN 250
-196°C – +185°C
DN 15 = PN 40
DN 25 = PN 45
Name
Argon
Chlorotrifluoromethane
Nitrous oxide
Ethane
Ethylene
Carbon dioxide
Carbon monoxide
Krypton
Methane
Oxygen
Nitrogen
Trifluoromethane
Argon
Nitrous oxide
Ethane
Ethylene
Helium
Krypton
LPG
Air
Methane
Neon
Oxygen
Nitrogen
Trifluoromethane
Hydrogen
Xenon
herose.com
Max. working pressure
250 bar
50 bar with use of O
2
DN 15 = 40 bar
DN 25 = 45 bar
17