7.3
Fault table
Fault
Leak at the stem
Leak between bonnet
and body
Leaking lateral
connections
Body leaking
Valve cannot be
changed over
7.4
Spare parts
Specialist workshops authorised by HEROSE!
We require the following details for your spare part orders:
article no. of the spare part package,
desired delivery quantity,
dispatch and delivery address,
desired method of dispatch.
7.5
Returns / complaints
Use the Service form in case of returns/complaints.
8
Disassembly and disposal
8.1
Notices regarding the disassembly
Take note of all national and local safety requirements.
The pipework system must be depressurised.
The medium and valve must be at ambient temperature.
Aerate / flush the pipework system in the case of corrosive and aggressive media.
22
Operating instructions
Cause
Gland nut loose
Packing gland defective
Fit on the stem damaged
Bonnet loose
Seal damaged
Inadequate seals
Blind plug / bolted-on safety
valves loose
Lateral connections cracked
Discontinuity/gas cavity open
Gland nut overtightened
Thread seized
Contact in case of service:
Herose.com › Service › Product service › Complaints
E-mail: service@herose.com
Fax: +49 4531 509 – 9285
Phone +49 4531 509-0
Remedy
Retighten the gland nut
Replace the valve
Replace the valve
Tighten the bolts
Replace the valve
Seal with suitable sealants
Tighten to the specified torques
Replace the valve
Replace the valve
Loosen the gland nut
Tightness must still be ensured
Replace the valve