9 Protocolo del centro de control
Address
Nombre
(no off-
set)
6
E4.1 Automatic adjustment not undertaken or in-
correct
7
E4.2 Desired target position could not be reached
when voltage failed (error blackstart)
8
E5.1 Residual capacity buffer
9
E5.2 Undervoltage buffer
10
E5.3 Error power supply
11
E6.1 Motor blocking
12
E6.2 Motor rough-running
13
E6.3 Tap change command cannot be performed,
timeout motor run
14
E7.1 Permanent signal microswitch
15
E7.2 Position fail, loss microswitch
16
Internal datapoint
17
Internal datapoint
18
Internal datapoint
19
Internal datapoint
20
Signal: blocking contact
21
Relay OK
22
Relay Error
1)
23
E2.1 Highest or lowest operating position reached BIT
1)
24
E2.2 Previous tap-change operation has not been
completed or fault motor-drive unit
1)
25
E2.3 Inrush interlock is active or automatic adjust-
ment required
1)
26
E2.4 Energy in the energy accumulator too low
1)
27
E2.5 Signal for blocking activated (door interlock
or temperature blocking)
28
Motor drive running
29
Ready for tap-change operation
30
Voltage failure (detection < 60 V, communication
impossible)
1)
31
E2.6 Error in wiring
Maschinenfabrik Reinhausen GmbH 2022
Type
Coil status
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
-
BIT
-
BIT
-
BIT
-
BIT
0 = door open
1 = door closed
BIT
1 = active
BIT
1 = active
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
BIT
1 = active
6117331/05 ES
EXTERNAL CONTROL
R = read / W = write
CONTROL PRO Others
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
-
-
-
-
-
-
-
-
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
®
®
ECOTAP
VPD
MD&C
101