Holding Register - MR ECOTAP VPD MD&C Instrucciones De Servicio

Publicidad

9 Protocolo del centro de control
Address
Nombre
(no offset)
0
Operating mode
▪ 1 = AVR AUTO
▪ 2 = AVR MANUAL
▪ 3 = EXTERNAL CONTROL
1
Tap position
2
Operations counter (MSB)
3
Operations counter (LSB)
4
Internal datapoint
5
Internal datapoint
6
P1 valor consigna
7
P2.1 Bandwith B1 (data value = 2 x set va-
lue; example: set value = 2.5 % => data va-
lue = 5)
8
P2.2 Delay time T1
9
P3.1 Bandwith B2 (data value = 2 x set va-
lue; example: set value = 4.5 % => data va-
lue = 9)
10
P3.2 Delay time T2
11
P4.1 Undervoltage blocking
12
P4.2 Overvoltage blocking
13
P7 Number of operating positions
14
P8.1 Lowest operating position
15
P8.2 Highest operating position
16
P6.1 Setting the target position (black start) UINT16
17
Tap-change operation (-3, -2, -1, +1, +2,
1)
+3)
18
Internal datapoint
19
P2.1 bandwidth 1
20
P2.1 bandwidth 1
21
P3.1 bandwidth 2
22
P3.1 bandwidth 2
31506
Internal datapoint
31507
Set baudrate
31508
Modbus ID
Tabla 21: Holding Register
Maschinenfabrik Reinhausen GmbH 2022

9.4.4 Holding Register

6117331/05 ES
Type
Unit
Decimal
places
UINT16
-
0
UINT16
-
0
SINT32
-
0
-
0
SINT32
-
-
-
-
UINT16
V
0
UINT16
%
0
UINT16
seconds
0
UINT16
%
0
UINT16
seconds
0
UINT16
V
0
UINT16
V
0
UINT16
-
0
UINT16
-
0
UINT16
-
0
-
0
UINT16
-
0
UINT16
-
-
FLOAT32 -
-
-
-
FLOAT32 -
-
-
-
UINT16
-
-
UINT16
Baud
0
UINT16
-
0
EXTERNAL CONTROL
R = read / W = write
CONTROL
Others
PRO
R
R
R
R
R
R
R
R
-
-
-
-
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
-
-
R
-
R
-
R
-
R
-
-
-
R/W
-
R/W
®
®
ECOTAP
VPD
MD&C
103