Address
Nombre
(no off-
set)
32200
AVR error (including E2.6, E3.x, E4.x, E5.x, E6.x
and E7.x)
32201
Out of bandwidth: Highest or lowest operating po-
sition reached + tap change command (AVR AU-
TO or EXTERNAL CONTROL)
Tabla 19: Discrete Inputs
Address
Nombre
(no offset)
0
Device number part 1/2
1
Device number part 2/2
2
Capacitor health
3
Input voltage (data value = 2 x measured
value; example: measured value = 125.5 V
=> data value = 251)
4
Voltage capacitor (data value = 10 x mea-
sured value; example: measured value =
10.6 V => data value = 106)
5
Software version year (YY)
6
Software version month (MM)
7
Software version day (DD)
8
Motor pause before next tap-change opera-
tion (data value = 10 x measured value;
example: measured value = 3 sec. => data
value = 30)
9
Status activation Modbus RTU (1 = active,
0 = inactive)
10
Remaining time to the next PreCheck
11
Internal datapoint
12
Input voltage
13
Input voltage
14
Buffer voltage
15
Buffer voltage
36600
Tap position
Tabla 20: Input Register
®
®
102
ECOTAP
VPD
MD&C
1)
El evento pertenece a la señalización de fallo colectiva E2 (dirección Mod-
bus 1)
9.4.3 Input Register
9 Protocolo del centro de control
Type
Coil status
BIT
1 = active
BIT
1 = active
Type
Unit
Decimal
places
SINT32
-
0
SINT32
-
0
UINT16
%
0
UINT16
V
0
UINT16
V
0
UINT16
-
0
UINT16
-
0
UINT16
-
0
UINT16
seconds
1
UINT16
-
0
UINT16
minutes
1
UINT16
-
-
FLOAT32 V
-
FLOAT32 V
-
FLOAT32 V
-
FLOAT32 V
-
UINT16
-
-
6117331/05 ES
EXTERNAL CONTROL
R = read / W = write
CONTROL PRO Others
-
-
EXTERNAL CONTROL
R = read / W = write
CONTROL PRO
R
R
R
-
-
R
R
R
R
-
-
-
-
-
-
-
-
Maschinenfabrik Reinhausen GmbH 2022
R
R
Others
R
R
R
R
R
R
R
R
R
R
R
-
R
R
R
R
R