condition of electric network.
F8.02 Selection of constant and variable torque
Range
Content
F8.02 can work switch constant torque, or variable torque, which is
suitable for different loads, protection level and related parameter.
Setting of over-voltage protection level
F8.03
default: Three phaseAC380V 650.0 One phaseAC220V 375
Range
F8.03 sets over-voltage protection level. Inverter tends to meet
over-voltage protection in low electric network. For the above
situation, the protection level may be adjusted down to guarantee
normal running of Inverter.
F8.04 Setting of low-voltage protection level
default: Three phaseAC380V 400 / One phaseAC220V 200
Range
Three phaseAC380V:380.0V~450.0V Unit
One phaseAC220V: 160.0V~220.0V
F8.04 sets voltage protection level. Inverter tends to meet low-voltage
protection in low electric network. Thus the value of F8.04 may be
adjusted down to guarantee normal running of Inverter.
F8.05 Setting of excess-temperature protection level
Range
F8.05 sets the excess-temperature protection level of Inverter. In
high temperature environment, the protection level may be adjusted
up to normal running of Inverter. However, much higher setting will
cause damage. The only solution is to increase effect of heat
elimination for the goal of cooling-down.
F8.06 Setting display of current filtering time
Range
Manual de Funcionamiento del variador de la serie H5000
Chapter 7 Detailed Explanations of Functional Parameters
0 – 1
0: Constant torque
Three phaseAC380V760K – 820.0V Unit
One phaseAC220V370.0V~420.0V
40 – 120
0 – 100
1: Variable torque
217
default: 0
Unit
1
0.1
0.1
default: 85℃/95℃
Unit
1
default: 2.0
Unit
1