1st line on display
phase error
ATEX - Mode
service mode
level controller
(=Level control)
intern. converter
20 mA => level
Signal contact 1-4
Language
DD.MM.YYYY
hh:mm
keylock
WLAN reset
Fault protocol
10
2nd line on display
(set value)
is activated
is deactivated
is activated
is deactivated
is activated
is deactivated
intern. converter
float switch
4-20mA Interface
matching
(=calibration)
1 - 1250 cm
Possible signals :
- Fault high water
- Collective fault
- Pump 1 on
- Pump 2 on
- Fault pump 1
- Fault pump 2
- system OK
Deutsch, English, etc...
see adjustments
on
off
DD.MM YYYY default
Signification
The energization of all the 3 phases and the
proper phase sequence at the mains input
are monitored.
To be disabled for 230 V pumps.
If the ATEX mode is enabled, it is not
possible to switch on the pump if the turn-off
level is under-run. This also applies for the
HAND function and the 24h starting.
If the service mode is disabled, it is
not possible to set the parameters. The
modification mode is only possible for the
service mode itself.
Level measurement via dynamic pressure
measurement
Level measurement via floating switch
Level measurement via external sensor
By pressing the key sequence
, the zero point of
the internal converter is adjusted. The
adjustment has to be carried out while
the pilot tube is emerged (with barometric
pressure). This adjustment is to be carried
out by a service technician only.
Final value of the sensor at 20 mA
Kind of signal on contacts 1-4
The collective fault signal can be timed
Setting of the menu language
Date and time
When the service mode is disabled, if the
keylock function is on, the screen locks after
3 minutes on the Home screen. To enter the
menu, press
for 3 seconds.
disabled
After having pressed the key
the protocol can be paged through by
pressing the keys
It is not possible to change the data.
.