3.1.4 Parameter setting

The following table shows the setting options and the effects of the individual parameters. A
parameter can be selected via the menu selection
For reasons of safety, the modification mode for the parameters can
only be enabled in the 'Stop'- operation (key
1st line on display
base load OFF
base load ON
high water
(High water HW)
run-time
(Run-time change after)
8
WARNING
2nd line on display
(set value)
Pump off ≤ Pump on
Peak load on < HW
And
HW ≤ final value of level
sensor
is deactivated
until 300 sec.
(see point 3.1.1).
).
Signification
Stop level pump
Modifications only during Stop-
operation!
Start level pump
Modifications only during Stop-
operation!
Flooding- alarm- level
WARNING
Additionally, this level is constantly
evaluated on the input for the
floating switch HW, independent
from the selected level transmitter.
Thereby, if necessary, 2 different
HV-levels can be realised with 2
different transmitters.
Modification only possible in Stop-
mode !
At transgression of the adjusted time the
pump is stopped shortly.
'DEACTIVATED' effects that the pump run is
not stopped abruptly.
This function eliminates potential
accumulations of air in the pump.
Here unto a time above the normal pump-
down time has to be adjusted. A switch
occurs if the requested pump has not
pumped down under the switch-on point
within the adjusted time. After 3 consecutive
the error "Run-time Alarm" occurs.