Models: EINSOLAR5V, EINSOLAR6.5V
1.
Product Overview
1. LCD&LED or LED
2. DC switch (optional)
H
3. PV Terminal (s)
4. Wi-Fi/GPRS Stick(optional)
5. Cable gland for Meter/DRM
6. AC Terminal
7. Second PE Terminal
1
Dimension:W×H×D=395 x 328 x 154mm
2.
Packing List
Mounting
Mounting
Inverter
Bracket
Accessories
1
1
1
3.
Installing
Installation Requirements
1. Please install the inverter(s) in places that can avoid
inadvertent contact.
2. Please install the inverter on solid/smooth surfaces.
3. The inverter(s) should not be installed near inflammable or
explosive objects.
AVOID
Direct
Rain
Snow
Lay up
Sunlight
Exposure
Quick Installation Guide
W
2
3
4
5
6
7
DC Plugs
Wi-Fi stick
AC Connector
MC4 or D4
(optional)
(optional)
2
1
1
Cable Specifications
No
Item
1
PE cable
2
AC Output
cable
3
DC Input
cable
4
Meter
D
5
DRED
3.1
Mounting
3.1.1 Use the mounting bracket as a template mark and drill holes of 10mm diameter and 70mm depth
3.1.2 Fix the mounting bracket with the screws and expansion bolts packed in mounting accessories
3.1.3 Attach the inverter to the mounting bracket
3.1.4 Check both sides of heat sink and ensure the inverter is stably attached
3.1.5 Use M5 screw (with T25 screwdriver, torque: 2.5Nm) to attach the heat sink fins to the mounting bracket
3.1.6 It is recommended to attach an anti-theft lock to the inverter
Step 1
160mm
Documents
1
Step 4
3.2
Installing the PE Cable
A second PE terminal is equipped at the bottom of the inverter.
Ensure the PE terminal is reliably grounded and the grounding resistance is
less than 10 Ohm.
Object
Description
Housing
1
2
M5 terminal lug with protective conductor
3
M5×13 pan head screw
Tighten it firmly into the housing (T25 screwdriver, torque: 2.5Nm).
NOTICE
Proper grounding connection of the second PE terminal and the AC terminal is mandatory. NOT properly connecting
both PE will void all product warranty.
Type
Specifications
Single-core outdoor copper cable
• Conductor cross-section: 4-6 mm²
Outdoor copper cable
• Conductor cross-section: 4-6 mm²
• Cable outer diameter: 9-14 mm
Standard outdoor PV cable,
• Conductor cross-section: 2.5-6 mm²
PV1-F Model recommended
• Cable outer diameter: 5-8 mm
Two-core outdoor shielded
• Conductor cross-section: 0.14-1.5 mm²
twisted pair cable
• Cable outer diameter: approx. 9 mm
CAT-5E, outdoor shielded cable
• Cable outer diameter: approx. 9 mm
Standard for EIA/TIA 568B
• cable maximum length 1000m
Step 2
160mm
10mm(2 ) Χ
Deep 70mm
Standby holes
Step 5
Step 3
Step 6
1
2
3