Descargar Imprimir esta página

Controller; Reflex Control Smart; Operator Panel; Default Settings - Reflex Reflexomat XS Manual De Instrucciones

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 39
Note!
The change in the filling level and the vessel pressure are indicated in
manual mode in the SmartControl app.
9

Controller

9.1

Reflex Control Smart

Access to the Reflexomat XS is possible using the Reflex Control Smart app via a
Bluetooth-connected smartphone or tablet. The app is available from the app
store (Android or iOS), or via the QR code given below.
The Reflex Control Smart app provides the following functions amongst others:
Intuitive and self-explanatory menu and operating guidance
Easy and quick commissioning (commissioning-wizard)
Querying of the system pressure
Individual configuration
Maintenance and troubleshooting wizard
Software updates for system control
Note!
Software updates for system control may only be executed via the app.
New available software updates are automatically displayed in the app.
9.2

Operator panel

1
Auto button/LED
The Auto button starts operation after commissioning or from
stop mode
The Auto LED illuminates green in Automatic mode
The Auto LED is off in stop mode
2
Pressure LED
The Pressure LED comes on in automatic mode
The Pressure LED flashes if there is a fault or during increasing
and decreasing of the pressure
3
Level LEDs
The level LEDs indicate the filling level in the vessel.
High water 3.1
Auto mode 3
Low water 3.3 (make-up requirement)
4
Stop button/LED
The stop button is for entering new values in the controller and
for manual mode (maintenance mode)
The Stop LED lights up in yellow
5
9.3
The device controller is shipped with the following default settings. Other
settings must be made during assisted commissioning using the Reflex Control
Smart app.

Default settings

Parameter
Next maintenance
Floating contact
Make-up
Make-up "ON"
Make-up "OFF"
Maximum make-up
quantity
Maximum make-up time
Maximum make-up cycles 6 cycles
Pressure maintenance
Compressor "ON"
Compressor "OFF"
"Compressor run time
exceeded" message
Outward flow solenoid
valve "CLOSE"
Outward flow solenoid
valve "OPEN"
Maximum pressure
Filling levels
Low water "ON"
Low water "OFF"
Solenoid valve in overflow
pipe "CLOSED"
9.4
Messages are displayed using the LEDs on the control panel with the meanings
specified in the table. A precise description of the LEDs,  9.2 "Operator panel",
 23. A detailed description of the error is available via the app.
LED
Auto
Stop
Service
Reflexomat XS — 02.16.2022 - Rev. A
Service button/LED
Warning and fault messages are acknowledged with the Service
button
The Service LED lights up in the event of a warning message
The Service LED flashes in the event of a fault message
Default settings
Setting
12 months
YES
8 %
12 %
0 Litres
30 minutes
within 2 hours
P
+ 0.3 bar
0
P
+ 0.4 bar
0
180 minutes
P
+ 0.4 bar
0
P
+ 0.5 bar
0
PSv – 0.3 bar
5 %
12 %
90 %

Messages

Function /
display
Button
LED lights up
Button
LED lights up
Button
LED lights up
LED flashes
Controller
Comment
Time left to the next due
maintenance.
 9.4 "Messages",  23.
Only when using a water meter.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressured added to
the "P
" minimum operating
0
pressure.
The message is displayed in the
app after compressor running of
180 minutes.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressured added to
the "P
" minimum operating
0
pressure.
Differential pressure as the
triggering pressure of the
response pressure of safety
valve "PSv".
Meaning
Start
Automatic operating mode
Maintenance / Interruption
Error
Acknowledge / Start Self-
Service
Warning
Error
English — 23

Publicidad

loading

Este manual también es adecuado para: