Hazard information
We accept no liability for damage to property or personal injury
caused by improper use or the failure to observe the hazard warn-
ings. In such cases, all warranty claims are void. We accept no liabil-
ity for any consequential damage.
The actuator is part of the building installation. Observe the relevant
national standards and directives during planning and set-up. The
device has been designed solely for operation on a 230 V/50 Hz AC
supply. Only qualified electricians (to VDE 0100) are permitted to
carry out work on the 230 V mains. The applicable accident preven-
tion regulations must be observed while such work is being carried
out. To avoid electric shocks from the device, please disconnect the
mains voltage (trip the miniature circuit-breaker). Non-compliance
with the installation instructions can cause fire or introduce other
hazards.
No SELV/PELV power circuits may be connected to the connecting
terminals of the relay outputs.
When connecting to the device terminals, take the permissible
cables and cable cross sections into account.
No SELV/PELV power circuits may be connected to the connecting
terminals of the relay outputs.
Exceeding this capacity could lead to the destruction of the device,
fires or electric shocks.
Please take the technical data (in particular the maximum permissible
switching capacity of the load circuits and the type of load to be
connected) into account before connecting a load. Do not exceed
the capacity specified for the device.
The circuit to which the device and the load will be connected must
be protected by a circuit breaker in accordance with EN60898-1
(tripping characteristic B or C, max. 16 A rated current, min. 6 kA
29