Installation and operation instruction
Actuator 24 V, 0÷10 V (with green indicators)
Fitting and Re-fitting
Do not connect power to the actuator unless the actuator is already fitted on the valve and
NEVER install the actuator in closed position - this may damage the valve. Actuator is sup-
plied in open position to ensure easy commissioning of the system.
Mount the actuator on the valve and finger tighten the connection union.
Do not use additional tools.
In case the actuator will have to be removed, it is recommended to electrically open the actuator by
activating DIP switch #6 for easier removal.
Hereafter, disconnect power and finger loosen the connection union.
Again, no need for additional tools.
Please make sure that the actuator is electrically opened, before re-fitting it on the valve.
Figure 1
Figure 2