8.2 MAINTENANCE UPDATE
SC_2VX
9. FAULT FINDING
Alarm message on the dis-
play
No AC
Pump P1 switched OFF
Pump P2 switched OFF
No pump activated
Levels sensors fault
P1 I=0 Amp
P2 I=0 Amp
P1 hydraulic issue
P2 hydraulic issue
P1 I>Imax
P2 I>Imax
Evacuation issue
10. FOR PROFESSIONALS
10.1 RETURN TO THE START-UP SCREEN
You can return to the settings made when the device was commis-
sioned by pressing the 4 arrow keys
In particular, the choice of the connected station can be changed.
10.2 EXPLANATION OF THE LEDS ON THE ELECTRONIC
BOARD
ALARM BOX
OFF/ALARM/ON
CCMOS
CLR CMOS
BMS1 NO
BMS1 NC
BMS2
LOOP P2
LOOP P1
AC POWER
The icone
indicates that the maintenance of the installation has to be done.
Once the maintenance has been done, enter a new frequency setting (see 6.2.3 Navigating the menu ): the
new maintenance date is set and the icon disappears.
Possible cause
No power supply.
Pump 1 deactivated
(activation lamp lights up red).
Pump 2 deactivated
(activation lamp lights up red).
Pumps deactivated
(activation lamps light up red).
Clogged sensor
Blocked sensor
Incorrect wiring of the sensors.
Incorrect connection of the sensors.
Incorrect position of the floats on the rail.
Float defective.
Pump disconnected.
Thermal break.
Defective pump.
Problem pump cover plate.
Impeller problem.
Clogged pipe.
Shut-off valve closed
Blockage of the pump.
Motor failure
Unable to evacuate water from the
station.
,
,
and
.
Blue LED
Sensors
Note: The pho-
tograph below
is used as an
example.
Red LED
deed, the lo-
BMS
cation of the
Green LED
LEDs may vary
Pumps
but the col-
ours and their
indications are
identical
all
electronic
boards.
Remedy
Check power supply.
Turn the current switch into position ON (I)
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
Reactivate the pumps by pressing the activation buttons.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
Clean the sensor, unclog the compression chambers.
Remove deposits in the tank.
Check that the floats move freely.
Remove deposits in the tank.
Check the wiring of the sensor terminals.
Check the correct location of the float connection on the casing.
Check the position of the floats.
Contact after-sales service.
Check pump connection.
Check the wiring of the pump terminals.
Pump connection occurs automatically after a delay.
Thermal break is a symptom of a malfunction that requires a
thorough check.
Check the pump.
Check pump hydraulics.
Check the discharge pipe.
Open the shut-off valve
Check for foreign bodies
Contact after-sales service.
Check for clogged discharge pipe.
Check that the shut-off valve is open.
Check that both pumps are working properly.
Blue LED: level indication
LED on = level sensor activated
Red LED: BMS operation
- LED on = event defined by the BMS condition is in progress
- LED off = no BMS event in progress
Green LED: pump operation
- LED on = pump running
- LED off = pump off
NOTICE
If the enclosure has been opened, take care not to
pinch or pull the cable when refitting the front panel.
10.3 LEARNING LOOPS
The management of the delay time in "Automatic" mode is not ad-
justable. It is calculated using a learning loop that averages the last 5
switch-ons.
In-
An increasing delay time is the symptom of a drop in output flow and
may therefore indicate a fault in the discharge installation (clogging, etc.).
11. GUARANTEE
Smart Control Box is guaranteed for 2 years for parts and labour, sub-
ject to correct installation, use and maintenance of the unit.
to