EN
General Instructions
Read these instructions carefully prior to
installation and use. Keep this manual for future
reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid should the product be used
in the manner intended and in accordance with the
instructions.
Application
EZ200 is a double panel radiant heater with
clean and simple design that blends well
with electrical fittings. EZ200 is intended for
total and supplementary heating as well as
protection against cold draughts from windows
in environments such as, department stores,
assembly halls, industrial premises etc.
The recommended installation heights for the
heater are shown on the introduction pages.
Protection class: IP44.
Operation
The panels have an operating temperature of
up to 320 °C and the heat is radiated to cold
surfaces. Max. surrounding temperature +30 °C.
Mounting
Elztrip is installed horizontally on ceilings,
in armature rails, on cables, suspended, etc.
Standard fittings for mounting are included
and are found inside the connection box. If
the heater is suspended by wires, use the four
mounting points on the heater. The distance
between panels should not be greater than the
height between panel and floor; i.e. (a) should
be less than (H), see illustration on introductory
page. For minimum distance, see diagrams on
introductory pages.
1. Determine the position of the panel on the
ceiling.
2. Bend the "legs" of the brackets approximately
90° (fig 1.1, 1.2).
3. Mount the brackets with an internal distance
according to dimensional drawing page 4,
on the ceiling or on a wire (fig 1.3). When the
panel is mounted on a wire put the bracket on
top of wire.
4. Mount the panel according to fig 1.4, start
with one end and then assemble the other
one.
5. Make sure that the screws are tightened.
6. When mounting on wire, use clips that
14
Elztrip EZ200
Installation and operating instructions
prevent the panel from sliding.
Electrical installation
Elztrip is intended for permanent installation.
The heaters are approved for serial connection.
The installation, which should be preceded by
an isolator switch with a contact separation
of at least 3 mm, should only be wired by a
competent electrician and in accordance with
the latest edition of IEE wiring regulations.
Electrical installation is performed via cable
glands in the junction box on top of the unit
(2 x Ø20,5 mm). The cable glands used must
meet the protection class requirements. The
largest cable diameter for the terminal block
is 16 mm². For serial connection the maximum
fuse size is 35A.
Control
When using this product as a local space
heater according to Ecodesign Regulation
(EU) 2015/1188, it must be supplemented with
one of the following approved controls. Please
note that a relaybox RB3 is required for 400V~
products.
• TAP16R, electronic thermostat that includes:
- Electronic room temperature control plus
week timer
- Room temperature control with open
window detection
• TAP16R and SKG30, black bulb sensor that
include:
- Electronic room temperature control plus
week timer
- Room temperature control with open
window detection
- Black bulb sensor
• TAP16R and PDK65, presence detector that
include:
- Electronic room temperature control plus
week timer
- Room temperature control with open
window detection
- Room temperature control with presence
detection
The product can be controlled in a different
way, e.g. by an overall control system (BMS),
but in that case the responsibility lies with the
installer to ensure that the control system is
programmed to make the installation meet
the requirements of Ecodesign Regulation
(EU) 2015/1188.