OPERATION
LOW OIL INDICATOR
See Figure 13.
The LOW OIL LED on the control panel will illuminate
when the unit is low or out of oil. The generator will not
start when the indicator is lit. To resume normal operation,
add engine oil as described earlier in this section. Do not
attempt to crank or start engine before it has been
properly serviced with recommended oil.
ECO MODE
See Figure 13.
NOTICE
the ECO mode switch in the OFF position. Allow the
engine speed to stabilize and the OUTPUT READY
LED to illuminate before putting the ECO mode switch
in the ON position.
NOTICE
parallel operation with another Westinghouse inverter
generator.
ECO mode minimizes fuel consumption and noise by
adjusting the engine RPM to the minimum required for the
current load.
Turn ECO mode ON when powering small appliances with
continuous loads such as a computer or electric light.
Turn ECO mode OFF when powering large surge loads
such as an air conditioner or electric pump.
To turn on ECO mode, verify that the OUTPUT READY
LED is illuminated, then push the switch to the ON
position. If no load is present, the generator RPM will
drop to idle speed. The generator will detect loads as
they are applied and increase engine RPM.
To run the generator at maximum power and RPM,
push the ECO mode switch to the OFF position.
OVERLOAD RESET
See Figure 13.
Do not overload the generator. If the generator is
approaching or has reached an overload condition, the
OVERLOAD LED on the control panel will illuminate.
If the generator is close to overloading, the OVERLOAD
LED will blink. Turn off and remove one or more
connected devices to decrease the load and resume
normal operation. If the load is not reduced, the unit will
reach an overload condition. To extend the service life
of the generator, avoid running the unit near capacity.
If the generator is overloaded or if there is a short circuit
in a connected device, the OVERLOAD LED will turn
solid, and the unit will automatically disconnect from
the load. The engine will continue to run, but there will
not be any electrical output.
18 | English
Always start the generator with
Do not use ECO mode when in
To restore electrical output after an overload:
l Remove any connected loads from the control panel
receptacles.
l Push the RESET button on the control panel until the
OVERLOAD LED goes OFF and the OUTPUT READY
LED is illuminated.
l Reset the circuit breaker(s) if activated.
l Verify that the intended running and surge loads do not
exceed the generator's capacity.
l Reconnect electrical loads sequentially, allowing the
generator to stabilize after each load is connected.
CIRCUIT BREAKERS
See Figure 13.
The 20 amp circuit breaker protects devices and
equipment connected to the 120V, 20 amp receptacles
from electrical overload. The 30 amp circuit breaker
protects devices and equipment connected to the
120V, 30 amp receptacles. If a circuit breaker activates,
turn off the connected device, remove it from the port or
outlet, and press the circuit breaker to reset.
USB PORTS
See Figure 13.
Use the USB ports and USB cables (not included)
to charge USB-compatible devices such as phones,
tablets, and speakers (up to 2.1 Amps).
NOTE: The USB ports are designed for charging
only and do not have data transfer or communication
capabilities.
PARALLEL OPERATION
See Figure 13.
WARNING
Never connect or disconnect the parallel cord leads
when a generator is running.
CAUTION
left and right cables is very important when the
generators are used with a transfer switch to supply
power to a building. To avoid serious personal
injury or damage to electrical devices, including the
generators, do not try to power an electrical system
in a building without using an approved transfer
switch.
NOTICE
is not compatible can cause a low voltage output
that can damage tools and appliances powered by
the generator.
Parallel operation gives you the ability to link to a
compatible Westinghouse Inverter Generator for
combined running and peak power output.
Fire and electrocution hazard.
Correct connection of the
Connecting to a generator that